  "name": "Standard 90.1-2019 vs 90.1-2022: modelled gross site energy use intensity by prototype building type",
  "description": "Per-prototype-building gross site energy use intensity (efficiency only, excluding on-site generation) under the 2019 and 2022 editions of ANSI/ASHRAE/IES Standard 90.1, with floor-area weights and percent savings, compiled from DOE's technical support document Tables ES.1 to ES.3.",
  "page": "https://casrai.org/guides/ashrae-standard-90-1",
  "publisher": "CASRAI",
  "license": "https://creativecommons.org/licenses/by/4.0/",
  "dateModified": "2026-11-19T03:05:01Z",
  "temporalCoverage": "2019/2022 editions",
  "spatialCoverage": "United States",
  "columns": [
    {
      "name": "Prototype building type",
      "unit": "",
      "description": ""
    },
    {
      "name": "Floor-area weight",
      "unit": "%",
      "description": ""
    },
    {
      "name": "Site EUI, 90.1-2019",
      "unit": "kBtu/ft2-yr",
      "description": ""
    },
    {
      "name": "Site EUI, 90.1-2022",
      "unit": "kBtu/ft2-yr",
      "description": ""
    },
    {
      "name": "Site energy savings",
      "unit": "%",
      "description": ""
    }
  ],
  "rows": [
    {
      "Prototype building type": "Small Office",
      "Floor-area weight": 3.8,
      "Site EUI, 90.1-2019": 28.2,
      "Site EUI, 90.1-2022": 25.7,
      "Site energy savings": 8.9
    },
    {
      "Prototype building type": "Medium Office",
      "Floor-area weight": 5,
      "Site EUI, 90.1-2019": 30.8,
      "Site EUI, 90.1-2022": 27.5,
      "Site energy savings": 10.7
    },
    {
      "Prototype building type": "Large Office",
      "Floor-area weight": 3.9,
      "Site EUI, 90.1-2019": 53.9,
      "Site EUI, 90.1-2022": 50.2,
      "Site energy savings": 6.9
    },
    {
      "Prototype building type": "Standalone Retail",
      "Floor-area weight": 10.9,
      "Site EUI, 90.1-2019": 46.8,
      "Site EUI, 90.1-2022": 39.3,
      "Site energy savings": 16
    },
    {
      "Prototype building type": "Strip Mall",
      "Floor-area weight": 3.7,
      "Site EUI, 90.1-2019": 50.2,
      "Site EUI, 90.1-2022": 40.6,
      "Site energy savings": 19.1
    },
    {
      "Prototype building type": "Primary School",
      "Floor-area weight": 4.8,
      "Site EUI, 90.1-2019": 43.9,
      "Site EUI, 90.1-2022": 41.6,
      "Site energy savings": 5.2
    },
    {
      "Prototype building type": "Secondary School",
      "Floor-area weight": 10.9,
      "Site EUI, 90.1-2019": 39.1,
      "Site EUI, 90.1-2022": 36.4,
      "Site energy savings": 6.9
    },
    {
      "Prototype building type": "Outpatient Healthcare",
      "Floor-area weight": 3.4,
      "Site EUI, 90.1-2019": 99.6,
      "Site EUI, 90.1-2022": 90.8,
      "Site energy savings": 8.8
    },
    {
      "Prototype building type": "Hospital",
      "Floor-area weight": 4.5,
      "Site EUI, 90.1-2019": 100.4,
      "Site EUI, 90.1-2022": 93,
      "Site energy savings": 7.4
    },
    {
      "Prototype building type": "Small Hotel",
      "Floor-area weight": 1.6,
      "Site EUI, 90.1-2019": 61.3,
      "Site EUI, 90.1-2022": 53.9,
      "Site energy savings": 12.1
    },
    {
      "Prototype building type": "Large Hotel",
      "Floor-area weight": 4.2,
      "Site EUI, 90.1-2019": 84.4,
      "Site EUI, 90.1-2022": 75,
      "Site energy savings": 11.1
    },
    {
      "Prototype building type": "Warehouse",
      "Floor-area weight": 18.6,
      "Site EUI, 90.1-2019": 13.8,
      "Site EUI, 90.1-2022": 12.8,
      "Site energy savings": 7.2
    },
    {
      "Prototype building type": "Quick-Service Restaurant",
      "Floor-area weight": 0.3,
      "Site EUI, 90.1-2019": 502.2,
      "Site EUI, 90.1-2022": 469.4,
      "Site energy savings": 6.5
    },
    {
      "Prototype building type": "Full-Service Restaurant",
      "Floor-area weight": 1,
      "Site EUI, 90.1-2019": 341.5,
      "Site EUI, 90.1-2022": 316.5,
      "Site energy savings": 7.3
    },
    {
      "Prototype building type": "Mid-Rise Apartment",
      "Floor-area weight": 13.7,
      "Site EUI, 90.1-2019": 39.3,
      "Site EUI, 90.1-2022": 35.5,
      "Site energy savings": 9.7
    },
    {
      "Prototype building type": "High-Rise Apartment",
      "Floor-area weight": 9.6,
      "Site EUI, 90.1-2019": 45.3,
      "Site EUI, 90.1-2022": 40,
      "Site energy savings": 11.7
    },
    {
      "Prototype building type": "National weighted average",
      "Floor-area weight": 100,
      "Site EUI, 90.1-2019": 47.8,
      "Site EUI, 90.1-2022": 43.1,
      "Site energy savings": 9.8
    }
  ],
  "sources": [
    {
      "title": "DOE/PNNL: ANSI/ASHRAE/IES Standard 90.1-2022 Energy Savings Analysis (Tables ES.1-ES.3)",
      "url": "https://www.energycodes.gov/sites/default/files/2024-02/Standard_90.1-2022_Final_Determination_TSD.pdf",
      "accessed": "2026-11-18"
    }
  ]
}