  "name": "AWWA Water Infrastructure Disinfection and Material Specifications",
  "description": "Original technical comparison of core ANSI/AWWA engineering, disinfection, and chemical standards detailing infrastructure scope, required chemical dosages, contact times, and mandatory post-treatment verification criteria compiled from official AWWA standards and regulatory frameworks.",
  "page": "https://casrai.org/guides/awwa-standards",
  "publisher": "CASRAI",
  "license": "https://creativecommons.org/licenses/by/4.0/",
  "dateModified": "2026-11-16T17:05:36Z",
  "temporalCoverage": "2024/2026",
  "spatialCoverage": "United States",
  "columns": [
    {
      "name": "Standard Designation",
      "unit": "",
      "description": "ANSI/AWWA official standard number and title"
    },
    {
      "name": "Infrastructure Scope",
      "unit": "",
      "description": "Covered water utility asset or material class"
    },
    {
      "name": "Disinfection Method",
      "unit": "",
      "description": "Primary chemical or operational methodology specified"
    },
    {
      "name": "Minimum Chemical Threshold",
      "unit": "mg/L",
      "description": "Required initial or applied chemical concentration"
    },
    {
      "name": "Minimum Contact Time",
      "unit": "hours",
      "description": "Mandatory retention or exposure duration"
    },
    {
      "name": "Mandatory Verification Metric",
      "unit": "",
      "description": "Analytical test required prior to placing infrastructure into service"
    }
  ],
  "rows": [
    {
      "Standard Designation": "ANSI/AWWA C651 (Water Mains - Continuous)",
      "Infrastructure Scope": "Underground potable water distribution pipelines",
      "Disinfection Method": "Continuous-feed chlorination",
      "Minimum Chemical Threshold": 25,
      "Minimum Contact Time": 24,
      "Mandatory Verification Metric": "Total coliform absence in two consecutive sample sets"
    },
    {
      "Standard Designation": "ANSI/AWWA C651 (Water Mains - Slug)",
      "Infrastructure Scope": "Potable distribution pipeline repairs and connections",
      "Disinfection Method": "High-dose slug chlorination",
      "Minimum Chemical Threshold": 100,
      "Minimum Contact Time": 3,
      "Mandatory Verification Metric": "Total coliform absence and turbidity compliance"
    },
    {
      "Standard Designation": "ANSI/AWWA C652 (Storage Tanks - Method 1)",
      "Infrastructure Scope": "Finished water storage reservoirs and elevated tanks",
      "Disinfection Method": "Full-fill chlorination",
      "Minimum Chemical Threshold": 10,
      "Minimum Contact Time": 24,
      "Mandatory Verification Metric": "Total coliform absence and residual test"
    },
    {
      "Standard Designation": "ANSI/AWWA C652 (Storage Tanks - Method 2)",
      "Infrastructure Scope": "Finished water storage reservoir surfaces and tanks",
      "Disinfection Method": "Surface spray or brush chlorination",
      "Minimum Chemical Threshold": 200,
      "Minimum Contact Time": 0.5,
      "Mandatory Verification Metric": "Total coliform absence in refilled water sample"
    },
    {
      "Standard Designation": "ANSI/AWWA C653 (Treatment Plants)",
      "Infrastructure Scope": "Water treatment facility basins, pipes, and filters",
      "Disinfection Method": "System-wide chemical chlorination",
      "Minimum Chemical Threshold": 25,
      "Minimum Contact Time": 24,
      "Mandatory Verification Metric": "Microbiological absence and disinfectant residual matching"
    },
    {
      "Standard Designation": "ANSI/AWWA C654 (Wells)",
      "Infrastructure Scope": "Gravel-wall and drilled groundwater production wells",
      "Disinfection Method": "Casing and aquifer gravel-pack chlorination",
      "Minimum Chemical Threshold": 50,
      "Minimum Contact Time": 12,
      "Mandatory Verification Metric": "Coliform absence in two samples collected 30 min apart"
    },
    {
      "Standard Designation": "ANSI/AWWA B300 (Hypochlorites)",
      "Infrastructure Scope": "Disinfection and oxidation treatment chemicals",
      "Disinfection Method": "Sodium and calcium hypochlorite chemical supply",
      "Minimum Chemical Threshold": 120000,
      "Minimum Contact Time": 0,
      "Mandatory Verification Metric": "Available chlorine assay and insoluble matter testing"
    }
  ],
  "sources": [
    {
      "title": "American Water Works Association Standards Portfolio",
      "url": "https://www.awwa.org/Publications/Standards",
      "accessed": "2026-11-16"
    },
    {
      "title": "U.S. EPA Drinking Water Regulatory Information and SDWA",
      "url": "https://www.epa.gov/dwreginfo/drinking-water-regulatory-information",
      "accessed": "2026-11-16"
    },
    {
      "title": "Electronic Code of Federal Regulations - 40 CFR Part 141",
      "url": "https://www.law.cornell.edu/cfr/text/40/141.21",
      "accessed": "2026-11-16"
    }
  ]
}