  "name": "Chemical storage control values from OSHA and university EHS programs",
  "description": "Numeric storage controls (cabinet capacities, container limits, separation distances, shelf and review requirements) compiled from the OSHA flammable-liquids standard, OSHA's Prudent Practices appendix and published university EHS storage programs; each row is traceable to the named source.",
  "page": "https://casrai.org/guides/chemical-storage-compatibility-segregation-rules",
  "publisher": "CASRAI",
  "license": "https://creativecommons.org/licenses/by/4.0/",
  "dateModified": "2026-11-23T00:09:54Z",
  "temporalCoverage": "2026",
  "spatialCoverage": "United States (University of Alberta row: Canada)",
  "columns": [
    {
      "name": "Storage control",
      "unit": "",
      "description": ""
    },
    {
      "name": "Value",
      "unit": "",
      "description": ""
    },
    {
      "name": "Unit",
      "unit": "",
      "description": ""
    },
    {
      "name": "Rule or paragraph",
      "unit": "",
      "description": ""
    },
    {
      "name": "Source",
      "unit": "",
      "description": ""
    }
  ],
  "rows": [
    {
      "Storage control": "Flammable cabinet capacity, Category 1-3 liquids",
      "Value": 60,
      "Unit": "gal per cabinet",
      "Rule or paragraph": "29 CFR 1910.106(d)(3)(i)",
      "Source": "OSHA 29 CFR 1910.106"
    },
    {
      "Storage control": "Flammable cabinet capacity, Category 4 liquids",
      "Value": 120,
      "Unit": "gal per cabinet",
      "Rule or paragraph": "29 CFR 1910.106(d)(3)(i)",
      "Source": "OSHA 29 CFR 1910.106"
    },
    {
      "Storage control": "Cabinet internal temperature limit in 10-minute fire test",
      "Value": 325,
      "Unit": "degF",
      "Rule or paragraph": "29 CFR 1910.106(d)(3)(ii)",
      "Source": "OSHA 29 CFR 1910.106"
    },
    {
      "Storage control": "Max glass or approved plastic container, Category 1",
      "Value": 1,
      "Unit": "pint",
      "Rule or paragraph": "Table H-12",
      "Source": "OSHA 29 CFR 1910.106"
    },
    {
      "Storage control": "Max glass or approved plastic container, Category 2",
      "Value": 1,
      "Unit": "quart",
      "Rule or paragraph": "Table H-12",
      "Source": "OSHA 29 CFR 1910.106"
    },
    {
      "Storage control": "Max glass or approved plastic container, Category 3",
      "Value": 1,
      "Unit": "gal",
      "Rule or paragraph": "Table H-12",
      "Source": "OSHA 29 CFR 1910.106"
    },
    {
      "Storage control": "Max glass or approved plastic container, Category 4",
      "Value": 1,
      "Unit": "gal",
      "Rule or paragraph": "Table H-12",
      "Source": "OSHA 29 CFR 1910.106"
    },
    {
      "Storage control": "Max safety can, Category 1",
      "Value": 2,
      "Unit": "gal",
      "Rule or paragraph": "Table H-12",
      "Source": "OSHA 29 CFR 1910.106"
    },
    {
      "Storage control": "Min separation between hazard classes without a barrier",
      "Value": 8,
      "Unit": "ft",
      "Rule or paragraph": "Cornell EHS guidance",
      "Source": "Cornell EHS"
    },
    {
      "Storage control": "Min distance, oxidizing gases from flammables",
      "Value": 20,
      "Unit": "ft",
      "Rule or paragraph": "Cornell EHS guidance",
      "Source": "Cornell EHS"
    },
    {
      "Storage control": "Hydrogen peroxide treated as liquid oxidizer above",
      "Value": 8,
      "Unit": "% H2O2",
      "Rule or paragraph": "Cornell EHS guidance",
      "Source": "Cornell EHS"
    },
    {
      "Storage control": "Organic acids at or above this concentration go in flammable cabinet",
      "Value": 80,
      "Unit": "% w/w organic acid",
      "Rule or paragraph": "Cornell EHS guidance",
      "Source": "Cornell EHS"
    },
    {
      "Storage control": "Flammable containers larger than this go in a flammable cabinet (Alberta)",
      "Value": 1,
      "Unit": "L",
      "Rule or paragraph": "University of Alberta",
      "Source": "University of Alberta"
    },
    {
      "Storage control": "Recommended max Class I and II liquids outside cabinet or safety can",
      "Value": 10,
      "Unit": "gal",
      "Rule or paragraph": "UNR EHS",
      "Source": "UNR EHS"
    },
    {
      "Storage control": "Open shelf lip height",
      "Value": 0.75,
      "Unit": "in",
      "Rule or paragraph": "Prudent Practices via 1910.1450 App A",
      "Source": "OSHA 1910.1450 App A"
    }
  ],
  "sources": [
    {
      "title": "OSHA 29 CFR 1910.106 Flammable liquids",
      "url": "https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.106",
      "accessed": "2026-11-22"
    },
    {
      "title": "Cornell EHS Chemical Storage (hazard class segregation)",
      "url": "https://ehs.cornell.edu/book/export/html/1482",
      "accessed": "2026-11-22"
    },
    {
      "title": "UNR EHS Chemical Hygiene Plan Chapter 16: Chemical Storage",
      "url": "https://www.unr.edu/ehs/policies-manuals/chemical-hygiene-plan/chapter-16",
      "accessed": "2026-11-22"
    },
    {
      "title": "OSHA 29 CFR 1910.1450 Appendix A (Prudent Practices, 2011)",
      "url": "https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.1450AppA",
      "accessed": "2026-11-22"
    },
    {
      "title": "University of Alberta Chemical Segregation",
      "url": "https://www.ualberta.ca/en/biological-sciences/safety/chemical-safety/chemical-segregation.html",
      "accessed": "2026-11-22"
    },
    {
      "title": "University of Houston EHS Chemical Storage and Segregation",
      "url": "https://uh.edu/ehs/labs/chemical-safety/chemical-storage-and-segregation/index.php",
      "accessed": "2026-11-22"
    }
  ]
}