  "name": "Flammable liquid storage cabinet requirements: federal OSHA 1910.106(d)(3) compared with Cal/OSHA 8 CCR 5533",
  "description": "Side-by-side comparison of the storage cabinet provisions in federal OSHA 29 CFR 1910.106(d)(3) and California's Cal/OSHA 8 CCR section 5533.",
  "page": "https://casrai.org/guides/flammable-liquid-storage-cabinet-requirements",
  "publisher": "CASRAI",
  "license": "https://creativecommons.org/licenses/by/4.0/",
  "dateModified": "2026-11-21T13:11:43Z",
  "temporalCoverage": "2026",
  "spatialCoverage": "United States; California",
  "columns": [
    {
      "name": "Provision",
      "unit": "",
      "description": ""
    },
    {
      "name": "Federal OSHA 29 CFR 1910.106(d)(3)",
      "unit": "",
      "description": ""
    },
    {
      "name": "Cal/OSHA 8 CCR 5533",
      "unit": "",
      "description": ""
    }
  ],
  "rows": [
    {
      "Provision": "Capacity, Category 1-3 liquids (gallons per cabinet)",
      "Federal OSHA 29 CFR 1910.106(d)(3)": "Not more than 60",
      "Cal/OSHA 8 CCR 5533": "Not more than 60"
    },
    {
      "Provision": "Capacity, Category 4 liquids (gallons per cabinet)",
      "Federal OSHA 29 CFR 1910.106(d)(3)": "Not more than 120",
      "Cal/OSHA 8 CCR 5533": "120 total of Category 1-4 (of which not more than 60 Category 1-3)"
    },
    {
      "Provision": "Number of cabinets per fire area",
      "Federal OSHA 29 CFR 1910.106(d)(3)": "No cabinet count stated in 1910.106(d)(3)",
      "Cal/OSHA 8 CCR 5533": "Up to 3; more in industrial occupancies if each group of up to 3 is at least 100 ft from other groups"
    },
    {
      "Provision": "Maximum internal temperature in fire test (F)",
      "Federal OSHA 29 CFR 1910.106(d)(3)": 325,
      "Cal/OSHA 8 CCR 5533": 325
    },
    {
      "Provision": "Fire test duration (minutes)",
      "Federal OSHA 29 CFR 1910.106(d)(3)": 10,
      "Cal/OSHA 8 CCR 5533": 10
    },
    {
      "Provision": "Fire test standard",
      "Federal OSHA 29 CFR 1910.106(d)(3)": "NFPA 251-1969",
      "Cal/OSHA 8 CCR 5533": "NFPA 251-1972"
    },
    {
      "Provision": "Label wording",
      "Federal OSHA 29 CFR 1910.106(d)(3)": "Flammable - Keep Fire Away",
      "Cal/OSHA 8 CCR 5533": "FLAMMABLE-KEEP FIRE AWAY"
    },
    {
      "Provision": "Metal cabinet: minimum sheet gauge",
      "Federal OSHA 29 CFR 1910.106(d)(3)": "No. 18 gage sheet iron",
      "Cal/OSHA 8 CCR 5533": "No. 18 gage sheet iron"
    },
    {
      "Provision": "Metal cabinet: air space between walls (inches)",
      "Federal OSHA 29 CFR 1910.106(d)(3)": 1.5,
      "Cal/OSHA 8 CCR 5533": 1.5
    },
    {
      "Provision": "Metal cabinet: door lock and sill",
      "Federal OSHA 29 CFR 1910.106(d)(3)": "Three-point lock; sill raised at least 2 in",
      "Cal/OSHA 8 CCR 5533": "Three-point lock; sill raised at least 2 in"
    },
    {
      "Provision": "Wood cabinet: minimum plywood thickness (inches)",
      "Federal OSHA 29 CFR 1910.106(d)(3)": 1,
      "Cal/OSHA 8 CCR 5533": 1
    }
  ],
  "sources": [
    {
      "title": "29 CFR 1910.106 Flammable liquids (OSHA)",
      "url": "https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.106",
      "accessed": "2026-11-21"
    },
    {
      "title": "8 CCR 5533 Storage cabinets (Cal/OSHA, California DIR)",
      "url": "https://www.dir.ca.gov/title8/5533.html",
      "accessed": "2026-11-21"
    }
  ]
}