  "name": "Protective relaying objectives and laboratory evidence",
  "description": "Editorial crosswalk compiled from USDA and PJM protection definitions and ORNL and SEL laboratory descriptions. The evidence column interprets how the reported observations relate to each objective; it is not a prescribed acceptance test, numerical benchmark or claim that one experiment validates a complete installation.",
  "page": "https://casrai.org/guides/protective-relaying",
  "publisher": "CASRAI",
  "license": "https://creativecommons.org/licenses/by/4.0/",
  "dateModified": "2026-11-14T13:48:29Z",
  "temporalCoverage": null,
  "spatialCoverage": null,
  "columns": [
    {
      "name": "Protection objective",
      "unit": "",
      "description": ""
    },
    {
      "name": "Meaning",
      "unit": "",
      "description": ""
    },
    {
      "name": "Relevant laboratory evidence",
      "unit": "",
      "description": ""
    },
    {
      "name": "Source basis",
      "unit": "",
      "description": ""
    }
  ],
  "rows": [
    {
      "Protection objective": "Dependability",
      "Meaning": "Correct response when protection is needed.",
      "Relevant laboratory evidence": "Relay trip conditions during modeled fault events.",
      "Source basis": "USDA 12.1.2.1; ORNL testbed report abstract"
    },
    {
      "Protection objective": "Security",
      "Meaning": "Avoiding inappropriate operation.",
      "Relevant laboratory evidence": "Comparing responses to events inside and outside the intended protection zone.",
      "Source basis": "USDA 12.1.2.2; PJM 2.2.4.2; SEL modeled fault testing; editorial crosswalk"
    },
    {
      "Protection objective": "Selectivity",
      "Meaning": "Isolating the minimum necessary circuits or equipment.",
      "Relevant laboratory evidence": "Relating the observed trip conditions to the modeled substation configuration.",
      "Source basis": "PJM 2.2.2; ORNL testbed report abstract; editorial crosswalk"
    },
    {
      "Protection objective": "Speed and event timing",
      "Meaning": "Clearing faults promptly while respecting dependability and security.",
      "Relevant laboratory evidence": "Synchronized timing and relay event observations; a trip output alone does not establish complete fault clearance.",
      "Source basis": "USDA 12.1.2.3; PJM 2.2.1; ORNL testbed report abstract"
    },
    {
      "Protection objective": "Input and communication verification",
      "Meaning": "Establishing which signals and messages reach the protection system.",
      "Relevant laboratory evidence": "Analog-signal checks, synchronized-time observations and message authentication.",
      "Source basis": "USDA 12.3.1.1; ORNL testbed report abstract"
    }
  ],
  "sources": [
    {
      "title": "USDA: Design Guide for Rural Substations, Chapter 12",
      "url": "https://www.rd.usda.gov/media/file/download/uep-bulletin-1724e-300.pdf",
      "accessed": "2026-11-14"
    },
    {
      "title": "PJM: Protective Relaying Philosophy and Design Guidelines, 2018",
      "url": "https://www.pjm.com/-/media/DotCom/committees-groups/subcommittees/rs/postings/protective-relaying-philosphy-and-design-guidelines.pdf",
      "accessed": "2026-11-14"
    },
    {
      "title": "ORNL: Assessment of the Electrical Substation-Grid Testbed, 2022",
      "url": "https://www.ornl.gov/publications/assessment-of-the-electrical-substation-grid-testbed-with-inside-outside-devices-and-distributed-ledger-technology/",
      "accessed": "2026-11-14"
    },
    {
      "title": "SEL: Protection Hardware-in-the-Loop Testing",
      "url": "https://selinc.com/solutions/protection-hil/",
      "accessed": "2026-11-14"
    }
  ]
}