  "name": "Secondary containment and spill-control requirements by storage situation: OSHA 1910.106, RCRA and SPCC",
  "description": "Compares what US federal regulations require for spill containment across chemical and oil storage situations: whether containment is required, its capacity basis and the key numeric limit. Compiled by CASRAI from the current text of 29 CFR 1910.106 (OSHA) and 40 CFR parts 112, 262 and 264 (EPA) as published in eCFR; state rules and permits can be stricter.",
  "page": "https://casrai.org/guides/secondary-containment-requirements-osha",
  "publisher": "CASRAI",
  "license": "https://creativecommons.org/licenses/by/4.0/",
  "dateModified": "2026-11-22T12:12:40Z",
  "temporalCoverage": "2026",
  "spatialCoverage": "United States (federal rules)",
  "columns": [
    {
      "name": "Storage situation",
      "unit": "",
      "description": ""
    },
    {
      "name": "Rule",
      "unit": "",
      "description": ""
    },
    {
      "name": "Containment required by this rule",
      "unit": "",
      "description": "As stated in the rule text"
    },
    {
      "name": "Capacity or design basis",
      "unit": "",
      "description": ""
    },
    {
      "name": "Key numeric limit",
      "unit": "",
      "description": ""
    },
    {
      "name": "Limit unit",
      "unit": "",
      "description": ""
    }
  ],
  "rows": [
    {
      "Storage situation": "Aboveground flammable liquid tanks in a diked area",
      "Rule": "29 CFR 1910.106(b)(2)(vii)(c)",
      "Containment required by this rule": "Yes (dike or drainage)",
      "Capacity or design basis": "Dike capacity not less than the greatest amount releasable from the largest tank, other tanks' volume below dike height deducted; walls liquidtight",
      "Key numeric limit": 6,
      "Limit unit": "ft maximum average dike wall height above interior grade"
    },
    {
      "Storage situation": "Aboveground flammable liquid tanks served by drainage",
      "Rule": "29 CFR 1910.106(b)(2)(vii)(b)",
      "Containment required by this rule": "Yes (drainage to impounding basin)",
      "Capacity or design basis": "Impounding basin not smaller than the largest tank served",
      "Key numeric limit": "",
      "Limit unit": "n/a"
    },
    {
      "Storage situation": "Outdoor storage of flammable liquid containers",
      "Rule": "29 CFR 1910.106(d)(6)(iii)",
      "Containment required by this rule": "Yes (grading or curb)",
      "Capacity or design basis": "Graded to divert spills away from buildings, or surrounded by a curb; provide drainage of ground or rain water",
      "Key numeric limit": 6,
      "Limit unit": "in. minimum curb height"
    },
    {
      "Storage situation": "Inside storage room for flammable liquids",
      "Rule": "29 CFR 1910.106(d)(4)(i)",
      "Containment required by this rule": "Yes (liquid-tight sill, ramp, recessed floor or grated trench)",
      "Capacity or design basis": "Noncombustible liquid-tight raised sills or ramps at openings, or floor below surrounding floor, or open-grated trench draining to a safe location",
      "Key numeric limit": 4,
      "Limit unit": "in. minimum sill or ramp height (or floor depth below surrounding floor)"
    },
    {
      "Storage situation": "Flammable liquid storage cabinet",
      "Rule": "29 CFR 1910.106(d)(3)",
      "Containment required by this rule": "No sump or spill containment stated",
      "Capacity or design basis": "Cabinet fire-resistance and capacity limits only; metal cabinet door sill raised above cabinet bottom",
      "Key numeric limit": 60,
      "Limit unit": "gal maximum Category 1-3 flammable liquid per cabinet (120 gal for Category 4; door sill at least 2 in.)"
    },
    {
      "Storage situation": "Hazardous waste containers at a permitted storage facility",
      "Rule": "40 CFR 264.175(b)",
      "Containment required by this rule": "Yes (containment system)",
      "Capacity or design basis": "Greater of 10% of container volume or volume of largest container; containers without free liquids excluded from the calculation",
      "Key numeric limit": 10,
      "Limit unit": "% of total container volume, or largest container if greater"
    },
    {
      "Storage situation": "Hazardous waste containers at an interim-status facility",
      "Rule": "40 CFR 265.175",
      "Containment required by this rule": "None stated: section reserved",
      "Capacity or design basis": "No text in current eCFR",
      "Key numeric limit": "",
      "Limit unit": "n/a"
    },
    {
      "Storage situation": "Small quantity generator central accumulation area",
      "Rule": "40 CFR 262.16(b)(2)",
      "Containment required by this rule": "No secondary containment stated for containers",
      "Capacity or design basis": "Container condition, closed containers, incompatible wastes not mixed, weekly inspection",
      "Key numeric limit": 7,
      "Limit unit": "days maximum interval between inspections (at least weekly)"
    },
    {
      "Storage situation": "Large quantity generator central accumulation area",
      "Rule": "40 CFR 262.17(a)(1)",
      "Containment required by this rule": "No general secondary containment stated for containers",
      "Capacity or design basis": "Weekly inspection; no general container containment stated in the paragraph",
      "Key numeric limit": 7,
      "Limit unit": "days maximum interval between inspections (at least weekly)"
    },
    {
      "Storage situation": "Satellite accumulation area",
      "Rule": "40 CFR 262.15(a)",
      "Containment required by this rule": "No secondary containment stated",
      "Capacity or design basis": "Container in good condition, closed, labelled; excess moved within three consecutive calendar days",
      "Key numeric limit": 55,
      "Limit unit": "gal maximum non-acute hazardous waste"
    },
    {
      "Storage situation": "Oil bulk storage containers (SPCC)",
      "Rule": "40 CFR 112.8(c)(2); 112.1(d)(2)(ii)",
      "Containment required by this rule": "Yes, for facilities above the SPCC threshold",
      "Capacity or design basis": "Entire capacity of the largest single container plus sufficient freeboard for precipitation; only containers of 55 gal or more count toward the threshold",
      "Key numeric limit": 1320,
      "Limit unit": "gal aggregate aboveground capacity threshold"
    },
    {
      "Storage situation": "Mobile or portable oil containers (SPCC)",
      "Rule": "40 CFR 112.8(c)(11)",
      "Containment required by this rule": "Yes, for facilities above the SPCC threshold",
      "Capacity or design basis": "Sufficient to contain the capacity of the largest single compartment or container; mobile refuelers and non-transportation-related tank trucks exempt",
      "Key numeric limit": "",
      "Limit unit": "n/a"
    }
  ],
  "sources": [
    {
      "title": "29 CFR 1910.106 Flammable liquids (OSHA)",
      "url": "https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.106",
      "accessed": "2026-11-22"
    },
    {
      "title": "40 CFR 264.175 Containment (eCFR)",
      "url": "https://www.ecfr.gov/current/title-40/section-264.175",
      "accessed": "2026-11-22"
    },
    {
      "title": "40 CFR 265.175 (eCFR)",
      "url": "https://www.ecfr.gov/current/title-40/section-265.175",
      "accessed": "2026-11-22"
    },
    {
      "title": "40 CFR 262.15 Satellite accumulation area (eCFR)",
      "url": "https://www.ecfr.gov/current/title-40/section-262.15",
      "accessed": "2026-11-22"
    },
    {
      "title": "40 CFR 262.16 Small quantity generators (eCFR)",
      "url": "https://www.ecfr.gov/current/title-40/section-262.16",
      "accessed": "2026-11-22"
    },
    {
      "title": "40 CFR 262.17 Large quantity generators (eCFR)",
      "url": "https://www.ecfr.gov/current/title-40/section-262.17",
      "accessed": "2026-11-22"
    },
    {
      "title": "40 CFR 112.1 and 112.8 SPCC (eCFR)",
      "url": "https://www.ecfr.gov/current/title-40/part-112",
      "accessed": "2026-11-22"
    }
  ]
}