ASTM E119: What the Fire-Resistance Test Measures and What Ratings Do Not Cover

ASTM E119 measures how long walls, floors, roofs and columns contain fire or carry load. See how ratings are set and what they do not cover.

Written and maintained by CASRAI Editorial Board

Last updated

Short answer

ASTM E119 is the standard test method for fire tests of building construction and materials. It measures how long a wall, partition, floor, roof, column or beam assembly can contain a fire, keep carrying its load, or both, when exposed to a set fire. The result is a rating in hours, such as one hour or two hours, that applies to the assembly as tested.

Definition and scope

ASTM E119 is titled Standard Test Methods for Fire Tests of Building Construction and Materials. According to its ASTM scope, it covers masonry unit assemblies and composite assemblies of structural materials, including loadbearing and other walls, partitions, columns, girders, beams, and floor and roof slabs. Its stated significance is to measure how long such elements contain a fire, retain structural integrity, or both, under a prescribed fire exposure. ASTM lists E119-26 as the active edition; the scope text summarized here is from E119-20, so confirm which edition a specification cites.

The standard classifies an assembly. It does not rate a single product in isolation, and ASTM states in section 1.2 that classifications shall not be construed as having determined suitability under other conditions.

How the test works in practice

A specimen is built to represent the construction and exposed to fire in a furnace. Testing laboratory Intertek describes the furnace as following a prescribed time-temperature curve; it also explains that performance is the time that passes before the first critical failure, whether that is a temperature rise on the unexposed side, flame or hot-gas projection through the assembly, or loss of the applied load.

What is measured depends on the element, per the ASTM scope:

  • Walls, partitions, floors and roofs: heat transmission, hot-gas transmission and, for loadbearing assemblies, load-carrying ability.
  • Beams and columns: load-carrying ability, taking account of restrained or unrestrained ends.

When a hose stream test is required, it follows the fire exposure and is carried out under ASTM Practice E2226. Intertek notes it is usually applied to wall assemblies and may be run on a duplicate sample. Results are reported as hours, for example 1/2-h, 2-h or 6-h, in the test report and in design listings.

Test requirements by element

The ICC-ES summary of E119 gives these specimen sizes and criteria. Treat them as that body’s summary and check the current edition of the standard for the controlling text.

Element Minimum exposed size (ICC-ES summary) Edge and load conditions or criteria noted
Loadbearing wall or partition At least 100 ft² exposed, neither dimension under 9 ft Vertical edges not restrained; must carry the load, not ignite cotton waste, and pass the hose stream
Non-loadbearing wall or partition Same size as above Restrained on all four edges
Column At least 9 ft exposed –
Floor or roof At least 180 ft² exposed, neither dimension under 12 ft Unexposed-surface temperature rise limit of 250°F (139°C) above the initial temperature

For protective membranes, the same summary treats an average thermocouple rise above 250°F, or any single reading above 325°F, over the initial temperature as failure.

What an E119 rating does not tell you

Section 4.4 of the standard lists what the test does not evaluate. The NZ Building Code Hub summary of E119-20 repeats the main limits. Use this as a checklist when a specification or product sheet cites E119:

  • Smoke and toxic gas: generation of smoke or toxic gases, and control of smoke passage, are not measured.
  • Surface flame spread: not measured. That is a different question from fire resistance.
  • Joints: fire behaviour of joints such as floor-to-wall and wall-to-wall is not evaluated.
  • Openings and penetrations: the effect of conventional openings such as outlets and plumbing penetrations is not included unless they were part of the tested construction.
  • Other lengths and components: performance of components or lengths other than those tested is not covered, and results are not directly applicable to different materials.

The NZ Building Code Hub also notes that the test does not by itself cover all factors of fire hazard or fire risk assessment, and Intertek describes results as a relative comparison of similar building elements.

Where it matters for labs and clinics

Laboratories and clinical buildings contain many wall, floor and corridor assemblies that are specified by fire-resistance hours, and many of them are pierced by utilities: outlets, plumbing and similar services. The limits above are the practical gaps for facilities staff. A rated assembly in a drawing or listing describes the construction that was tested; whether a particular penetration or joint is covered depends on what the listing includes. When a project cites E119, useful questions to put to the designer or supplier are which tested assembly is meant, which edition applies, and whether the penetrations and joints in question are part of the tested construction.

Fire-resistance ratings sit alongside other safety rules for these buildings. For the wider framework, see CASRAI’s guides to the NFPA 101 Life Safety Code and the NFPA 99 Health Care Facilities Code. For storage hazards in the same spaces, see flammable liquid storage cabinet requirements and compressed gas cylinder storage requirements.

Common misunderstandings

  • “Fire-rated” means fireproof. A rating is a time under a defined test exposure, not a guarantee beyond that exposure.
  • A rating covers the whole wall system. It covers the tested assembly; joints and penetrations are outside the test unless they were included.
  • A rating says something about smoke. Smoke generation and smoke passage are not measured by E119.
  • The rating transfers to any size or material. ASTM states the classification does not determine suitability under other conditions.
  • E119 is the only equivalent. The NZ Building Code Hub describes ASTM E119-20 as similar to UL 263.

Sources

Follow CASRAI

Research-administration guidance, standards updates and independent tool reviews.

Ask CASRAI · free to try

Ask about ASTM E119: What the Fire-Resistance Test Measures and What Ratings Do Not Cover

Ask your first 2 questions free below. Subscribers get 150 a day for $29 a month.

An AI assistant specialized in research administration. It cites the sources behind every answer, labels web answers and says when it can't answer.

Answers draw on CASRAI's guides and dictionary plus the federal and funder documents we index: Federal Register, Grants.gov, Regulations.gov and UKRI.

Works on this site and inside Claude, Cursor and the AI tools you already use.

Everything CASRAI publishes — this page, the dictionary, the guides and the news — stays free to read, with no account and no card.

Referenced across the research world

University of Cambridge logoColumbia University logoCrossref logoUniversity of Edinburgh logoHarvard University logoUniversity of Oxford logoPrinceton University logoStanford School of Medicine logoUniversity College London logoORCID logoUniversity of Cambridge logoColumbia University logoCrossref logoUniversity of Edinburgh logoHarvard University logoUniversity of Oxford logoPrinceton University logoStanford School of Medicine logoUniversity College London logoORCID logo
  • University of Cambridge logo
  • Columbia University logo
  • Crossref logo
  • University of Edinburgh logo
  • Harvard University logo
  • University of Oxford logo
  • Princeton University logo
  • Stanford School of Medicine logo
  • University College London logo
  • ORCID logo

View CASRAI adoption →