Functional Safety: Standards, SIL & ASIL Guide

A technical guide to functional safety standards, safety integrity levels (SIL), automotive ASIL metrics, and automated laboratory safety applications.

Written and maintained by CASRAI Editorial Board

Published

On this page

Functional safety is the part of overall system safety that depends on electrical, electronic, and programmable electronic (E/E/PE) safety-related systems operating correctly in response to their inputs, ensuring equipment transitions to and remains in a predictable safe state whenever hazardous operational anomalies or hardware faults occur.

Unlike passive safety measures such as blast-resistant enclosures, chemical containment dikes, or emergency eye-wash stations, functional safety relies on active automated detection, electronic logic evaluation, and controlled physical intervention. When an automated chemical feed runaway develops, an industrial robot breaches a protective perimeter, or an autonomous vehicle sensor reports conflicting data, a functionally safe architecture senses the deviation, computes the required protective response, and drives final control elements to arrest the hazard before injuries, environmental contamination, or equipment destruction occur.

Definition and Scope of Functional Safety

The foundational international standard for functional safety, IEC 61508, formally defines the discipline across the interaction of three distinct entities: the Equipment Under Control (EUC), the EUC control system, and one or more dedicated safety-related systems. The EUC encompasses the physical apparatus, machinery, or process plant whose operation entails inherent physical or chemical hazards—such as an automated synthesis reactor, a high-pressure autoclave, or a motor test dynamometer. The EUC control system, commonly termed the Basic Process Control System (BPCS) in process plants, governs normal operational setpoints, recipe execution, and yield optimization. Safety-related systems, by contrast, remain dedicated exclusively to monitoring critical variables, detecting uncommanded excursions, and executing safety functions to preserve or restore a safe state when normal process controls fail.

To understand the scope of functional safety, engineers establish clear boundaries between functional safety and adjacent engineering and risk-management disciplines:

  • Active versus Passive Safety: Passive safety incorporates structural barriers, fireproofing insulation, and gravity drainage channels that mitigate consequences without dynamic decision-making or power sources. Functional safety requires an energized sensing loop, decision logic, and actuator stroke to execute a defined safety instrumented function.
  • Random Hardware Faults versus Systematic Failures: Functional safety treats hardware degradation and random physical failures (such as semiconductor gate breakdown, resistor drift, or mechanical seal wear) using quantitative probability models. In contrast, systematic errors—including software coding bugs, specification ambiguities, electrical crosstalk, and maintenance oversights—are eliminated or minimized through rigorous development lifecycles, structured verification, and deterministic quality assurance procedures.
  • Safety of the Intended Functionality (SOTIF): Governed in the automotive sector by ISO 21448, SOTIF addresses hazards resulting from functional insufficiencies or performance limitations in the absence of a system fault. Examples include radar clutter in heavy rainfall, machine learning camera misclassifications under glare, or ultrasonic sensor dead zones. While traditional functional safety asks whether the hardware and software executed their design intent without component failure, SOTIF analyzes whether the design intent itself remains safe under complex real-world operational environments.
  • Industrial Cybersecurity: Codified under IEC 62443 and ISO/SAE 21434, cybersecurity protects automated systems from deliberate unauthorized digital manipulation. Because an intentional intrusion can disable or corrupt safety interlocks, functional safety and security lifecycles must interface continuously: a safety-related system that lacks cyber resilience cannot guarantee functional integrity under adverse network conditions.
  • Occupational and Process Safety: Functional safety constitutes one specific technological layer within broader enterprise safety management. It supports, but does not replace, administrative protocols, chemical hygiene plans, toxicological exposure controls, and standard operating procedures.

How Functional Safety Operates Across the Safety Lifecycle

Functional safety cannot be retrofitted into a completed facility through component swaps or isolated testing. International standards mandate a structured safety lifecycle that spans from initial concept formulation through decommissioning. IEC 61508 and sector-specific standards like IEC 61511 organize this lifecycle into sequential, iterative phases designed to manage both random and systematic risks.

The safety lifecycle begins with comprehensive hazard identification and risk assessment. Multi-disciplinary teams conduct structured reviews using techniques such as Hazard and Operability (HAZOP) analysis and Failure Modes and Effects Analysis (FMEA). When evaluating chemical and laboratory facilities, teams reference established requirements for Process Hazard Analysis to catalog every conceivable deviation in pressure, temperature, flow rate, and reactant composition. For complex human-machine interfaces, teams integrate Use FMEA and usability analysis to identify how human errors or confusing alarm layouts could compromise system stability.

Once hazards are documented, engineers determine the risk reduction required to bring each hazardous event below an organization’s tolerable risk threshold. Using techniques such as Layer of Protection Analysis (LOPA) or risk graphs, safety functions are allocated to distinct protection layers. Functions implemented via electronic systems are formally designated as Safety Instrumented Functions (SIFs), each assigned a target Safety Integrity Level (SIL).

Engineers then author the Safety Requirements Specification (SRS). The SRS serves as the authoritative design contract, specifying process safe states, maximum allowable process safety times, sensor voting logic, environmental ratings, manual emergency overrides, and required proof-test intervals. During the design and realization phase, hardware architectures are built to satisfy target reliability metrics and architectural fault tolerance constraints. Concurrently, software development follows strict V-model lifecycles incorporating static code analysis, unit testing, requirements traceability, and formal verification.

Following installation, the lifecycle mandates rigorous Factory Acceptance Testing (FAT) and Site Acceptance Testing (SAT) before hazardous materials or mechanical energies are introduced. During the operational phase, facility personnel perform periodic proof testing at predefined intervals to reveal latent, unannounced dangerous failures. Finally, strict Management of Change (MOC) procedures govern every hardware replacement, sensor recalibration, and firmware patch to ensure modifications do not degrade established safety margins.

Worked Engineering Example: Layer of Protection Analysis (LOPA)

To illustrate how functional safety risk reduction is quantified in engineering practice, consider an automated 100-liter jacketed chemical synthesis reactor processing an energetic organic intermediate. The reactor employs an automated control loop to circulate chilled heat-transfer fluid through the jacket to remove exothermic reaction heat.

  • Initiating Event: Failure of the primary circulation pump or control valve in the Basic Process Control System (BPCS), leading to loss of cooling. Based on facility operating history and equipment reliability databases, this initiating event occurs at an estimated frequency of $f_{text{init}} = 1.0$ event per year ($1.0 times 10^{0} / text{year}$).
  • Consequence Severity: If cooling is lost, exothermic thermal runaway ensues within 8 minutes, causing solvent boiling, reactor overpressurization, and structural rupture with potential operator fatalities from toxic vapor release. Corporate risk criteria categorize this as a Major Consequence, establishing a tolerable event frequency limit of $f_{text{tol}} = 1.0 times 10^{-4}$ events per year.
  • Existing Independent Protection Layers (IPLs): The facility identifies two qualified IPLs that operate independently of the BPCS and each other:
    • IPL 1 (Operator Intervention): A high-temperature alarm alerts control room personnel. Because the process safety time is 8 minutes, and standard human reliability standards require at least 10 to 15 minutes for verified human response in complex scenarios, this layer cannot qualify as a fully independent protection layer under IEC 61511 rules without automated assist. If emergency procedures allow a simple manual deluge button within immediate reach, standard LOPA credits assign a conservative Probability of Failure on Demand of $PFD = 1.0 times 10^{-1}$ (a Risk Reduction Factor of 10).
    • IPL 2 (Mechanical Rupture Disk): A certified bursting disk sized to vent reactor vapor directly to an emergency catch tank. When maintained under a documented inspection program, this passive device provides a credited $PFD = 1.0 times 10^{-2}$ (a Risk Reduction Factor of 100).
  • Risk Reduction Calculation: Combining the initiating event frequency and qualified IPLs yields the intermediate mitigated event frequency:

$$f_{text{mitigated}} = f_{text{init}} times PFD_{text{IPL1}} times PFD_{text{IPL2}} = 1.0 times 10^{0} times 1.0 times 10^{-1} times 1.0 times 10^{-2} = 1.0 times 10^{-3} / text{year}$$

Because the intermediate frequency ($1.0 times 10^{-3} / text{year}$) remains higher than the tolerable risk target ($1.0 times 10^{-4} / text{year}$), an additional risk reduction gap of at least a factor of 10 exists:

$$text{Target } PFD_{text{avg}} = frac{f_{text{tol}}}{f_{text{mitigated}}} = frac{1.0 times 10^{-4}}{1.0 times 10^{-3}} = 1.0 times 10^{-1}$$

$$text{Required Risk Reduction Factor (RRF)} = frac{1}{PFD_{text{avg}}} = frac{1}{0.10} = 10$$

This quantitative gap requires an independent Safety Instrumented Function (SIF) rated for Safety Integrity Level 1 (SIL 1, low-demand $PFD_{text{avg}}$ between $1.0 times 10^{-2}$ and $1.0 times 10^{-1}$). To achieve this SIF, safety engineers implement dedicated, redundant temperature transmitters, an independently powered safety logic solver, and a fast-acting automated chemical inhibitor injection valve that quenches the runaway reaction automatically within 90 seconds of high-temperature trip detection.

Core Standards, Integrity Levels, and Architectural Constraints

While IEC 61508 serves as the horizontal umbrella standard across all electrical, electronic, and programmable safety-related systems, distinct industries have derived tailored vertical standards to address sector-specific operating profiles, regulatory frameworks, and failure physics:

  • IEC 61511 / ANSI/ISA-84 (Process Industry Sector): Governs chemical processing, petrochemical refining, oil and gas extraction, and pharmaceutical manufacturing. It focuses predominantly on low-demand Safety Instrumented Systems (SIS) executing automated shutdown, depressurization, and deluge functions.
  • ISO 26262 (Road Vehicles): Tailors functional safety to series-production passenger automobiles and commercial vehicles. It governs electrical and electronic architectures, embedded software, and semiconductor intellectual property through Automotive Safety Integrity Levels (ASIL A through ASIL D).
  • IEC 62061 and ISO 13849-1 (Machinery Safety): Focuses on industrial robotics, automated material handling, packaging machinery, and assembly automation. ISO 13849-1 classifies systems by Performance Levels (PL a through PL e) and circuit Categories (B, 1, 2, 3, 4), while IEC 62061 applies SIL assignments to machine control loops.
  • SAE ARP4754A, RTCA DO-178C, and RTCA DO-254 (Aerospace & Avionics): Establishes system-level safety assessments and allocates Development Assurance Levels (DAL A through DAL E) to airborne software and complex electronic hardware based on aircraft-level failure conditions (Catastrophic, Hazardous, Major, Minor).
  • IEC 62304 and IEC 60601-1 (Medical Devices): Classifies medical device software lifecycles into software safety classes (Class A, B, C) based on potential injury severity to patients or clinical operators.

Mathematical Formulations of Safety Integrity

Under IEC 61508, the quantitative reliability of a safety function depends on its demand mode. In low-demand mode (where demands on the safety system occur no more than once per year), performance is measured as the Average Probability of Failure on Demand ($PFD_{text{avg}}$). In high-demand or continuous mode (where demands occur more frequently than once per year, or where the system operates in continuous regulation), performance is evaluated as the Average Frequency of Dangerous Failure per Hour ($PFH$).

Component failure rates are partitioned into four mutually exclusive categories: Safe Detected ($lambda_{SD}$), Safe Undetected ($lambda_{SU}$), Dangerous Detected ($lambda_{DD}$), and Dangerous Undetected ($lambda_{DU}$). The total component failure rate is the sum $lambda = lambda_S + lambda_D = lambda_{SD} + lambda_{SU} + lambda_{DD} + lambda_{DU}$. Dangerous undetected failures represent the primary threat to life and asset integrity because an unrevealed fault leaves the safety function disabled without operator awareness until a real demand occurs or a proof test is performed.

For a basic single-channel (1oo1) subsystem operating in low-demand mode, $PFD_{text{avg}}$ is approximated by the classical safety reliability equation:

$$PFD_{text{avg}} approx frac{1}{2} lambda_{DU} T_1 + lambda_{DD} MTTR$$

Where $T_1$ represents the periodic proof-test interval (in hours) and $MTTR$ represents the Mean Time to Restoration. Because dangerous detected faults are rapidly annunciated and repaired (with typical $MTTR$ values of 8 to 24 hours), the term $frac{1}{2} lambda_{DU} T_1$ dominates the equation. Consequently, extending the interval between proof tests directly inflates the unreliability of the safety loop, regardless of component quality.

Safe Failure Fraction and Hardware Fault Tolerance

Meeting a numerical $PFD_{text{avg}}$ or $PFH$ target is necessary but not sufficient for SIL compliance. IEC 61508-2 enforces architectural constraints via the Safe Failure Fraction (SFF) and Hardware Fault Tolerance (HFT):

$$SFF = frac{sum lambda_S + sum lambda_{DD}}{sum lambda_S + sum lambda_D} = frac{lambda_{SD} + lambda_{SU} + lambda_{DD}}{lambda_{SD} + lambda_{SU} + lambda_{DD} + lambda_{DU}}$$

Subsystems are categorized as Type A (simple devices with well-characterized failure modes and exhaustive failure data, such as discrete relays, check valves, and analog solenoids) or Type B (complex programmable devices, including microcontrollers, DSPs, smart transmitters, and safety PLCs). The table below outlines the architectural constraints enforced by IEC 61508-2, dictating the minimum Hardware Fault Tolerance required for each subsystem type:

Safe Failure Fraction (SFF) Type A: HFT = 0 Type A: HFT = 1 Type B: HFT = 0 Type B: HFT = 1
Below 60% SIL 1 SIL 2 Not Allowed SIL 1
60% to 90% SIL 2 SIL 3 SIL 1 SIL 2
90% to 99% SIL 3 SIL 4 SIL 2 SIL 3
99% or Greater SIL 3 SIL 4 SIL 3 SIL 4

As shown in the architectural constraints matrix, a complex Type B controller with an SFF between 60% and 90% can achieve at most SIL 1 in a single-channel configuration (HFT = 0). Achieving SIL 2 or SIL 3 requires adding hardware redundancy (such as a 1oo2 dual-channel architecture, providing HFT = 1) or integrating advanced internal diagnostic self-tests that elevate the SFF above 90% or 99%.

Automotive Safety Integrity Levels (ISO 26262)

In the automotive sector, ISO 26262 governs electrical and electronic safety for road vehicles. Rather than assessing overall facility risk, vehicle engineers perform a Hazard Analysis and Risk Assessment (HARA) at the item level. Each hazardous operational event is classified across three independent parameters:

  • Severity (S0 to S3): Measures the potential injury extent to vehicle occupants or pedestrians, ranging from S0 (no injuries) and S1 (light to moderate injuries) to S3 (life-threatening or fatal injuries).
  • Exposure (E0 to E4): Evaluates the operational likelihood of being in the situation where the hazard manifests, ranging from E0 (extremely unlikely) to E4 (high probability, encountered in daily driving).
  • Controllability (C0 to C3): Evaluates whether an average driver or bystander can avoid injury once the failure occurs, ranging from C0 (controllable in general) to C3 (difficult or impossible to control).

The combination of S, E, and C determines the assigned Automotive Safety Integrity Level, ranging from Quality Management (QM, standard automotive engineering rigor) through ASIL A, ASIL B, ASIL C, and ASIL D (the most stringent level, applied to critical steering, braking, and battery isolation functions). To demonstrate compliance at the hardware level, ISO 26262-5 establishes strict quantitative metric thresholds:

  • Single-Point Fault Metric (SPFM): Evaluates hardware coverage against faults that directly violate a safety goal without a secondary failure. ASIL B recommends $ge 90%$, ASIL C mandates $ge 97%$, and ASIL D mandates $ge 99%$.
  • Latent Fault Metric (LFM): Evaluates hardware coverage against latent multiple-point faults that remain unrevealed until an independent secondary fault occurs. ASIL B recommends $ge 60%$, ASIL C mandates $ge 80%$, and ASIL D mandates $ge 90%$.
  • Probabilistic Metric for Random Hardware Failures (PMHF): Sets an absolute quantitative ceiling on dangerous random hardware failure rates per operating hour, expressed in Failures in Time ($1 text{ FIT} = 10^{-9} text{ failures/hour}$). ASIL B and ASIL C enforce a ceiling of $< 100 text{ FIT}$ ($< 10^{-7} / text{hour}$), while ASIL D enforces $< 10 text{ FIT}$ ($< 10^{-8} / text{hour}$).

The structured data table below compares quantitative integrity thresholds, failure bounds, and cross-sector equivalencies across IEC 61508, ISO 26262, and aerospace standards, providing direct references for engineering cross-walks.

Functional Safety in Laboratories, Pilot Plants, and Supply Decisions

While functional safety standards originated in heavy petrochemical processing and commercial automotive manufacturing, modern automated research laboratories and pilot testing facilities increasingly operate within their scope. As research institutions scale up continuous-flow chemical synthesizers, automated robotic pipetting suites, high-pressure hydrogen reactors, and battery pack testing dynamometers, electronic controls replace physical fume-hood sash barriers as primary hazard defenses.

In chemical research environments, functional safety directly intersects toxic and flammable gas handling. Automated gas detection heads in toxic storage vaults must trigger emergency ventilation purge fans and shut off cylinder pneumatic manifold valves within designated process safety times. When these systems fail due to bypassed interlocks, neglected sensor calibrations, or uncertified relays, severe incidents occur. Investigations published by the Chemical Safety Board frequently cite unverified interlocks, lack of independent safety layers, and failure to perform proof tests as root contributors to industrial and laboratory runaway explosions.

Similarly, automotive and aerospace research dynamometer cells require certified functional safety interlocks. When testing experimental battery management systems (BMS) or electric powertrain inverters, an uncommanded torque surge or battery thermal runaway demands millisecond-level contactor opening via certified ASIL D safety relays. Standard building automation controllers or lab supervisory computers cannot provide the necessary hardware fault tolerance or diagnostic coverage to guarantee operator protection.

Research organizations maintain compliance and regulatory tracking across multiple automated systems by deploying dedicated chemical safety software. These digital platforms track chemical inventory thresholds, schedule mandatory proof-test intervals for safety-related instrumentation, and record sensor calibration certificates required during regulatory audits.

Procurement and Technical Evaluation Checklist for Safety Equipment

When acquiring automated laboratory equipment, pilot plant skids, or safety-critical instrumentation, procurement officers and laboratory engineering teams must conduct structured technical due diligence. Sourcing decisions should adhere to a standardized evaluation framework:

  1. Third-Party Certification Verification: Inspect the manufacturer’s Certificate of Functional Safety issued by an accredited certification body (such as TÜV SÜD, TÜV Rheinland, or exida). Confirm that the certification explicitly references IEC 61508 or IEC 61511 and certifies the specific model number, firmware version, and target SIL.
  2. Safety Manual Review: Request and analyze the manufacturer’s official Safety Manual before purchase. The safety manual defines essential operational constraints, including maximum operating temperature, vibration limits, required proof-test procedures, diagnostic test intervals, and mandatory de-energization wiring topologies.
  3. FMEDA Report and Failure Rate Disclosure: Verify that the vendor supplies a complete Failure Modes, Effects, and Diagnostic Analysis (FMEDA) report. The report must provide itemized failure rates ($lambda_{SD}, lambda_{SU}, lambda_{DD}, lambda_{DU}$), Safe Failure Fraction (SFF), and Hardware Fault Tolerance (HFT). Vague marketing claims of general reliability or Mean Time Between Failures (MTBF) are unacceptable, as MTBF aggregates safe and dangerous failures without distinction.
  4. Proof-Testing Feasibility: Assess whether the laboratory facility can realistically execute the vendor’s mandated proof-test procedure. If achieving the claimed $PFD_{text{avg}}$ requires physically removing a sensor every six months for full-stroke testing in an off-site calibration bath, evaluate whether operational staffing can support this cadence or if a redundant architecture with online proof testing should be procured instead.
  5. Systematic Capability (SC Rating): Check the Systematic Capability rating (SC 1, SC 2, or SC 3) of the equipment’s firmware and configuration tools. Systematic capability reflects the vendor’s software development quality assurance; using an SC 2 sensor in an SIL 3 safety loop violates IEC 61508-2 systematic integrity rules, regardless of hardware redundancy.
  6. Supplier Quality and Change Governance: Follow a documented workflow for supplier risk assessment to evaluate the vendor’s internal change-management procedures. The vendor must provide formal contractual commitments to notify customers of newly discovered component errata, safety advisories, and firmware revisions throughout the operational lifecycle of the equipment.

Common Misunderstandings About Functional Safety

Engineering teams and procurement managers frequently encounter persistent misconceptions regarding functional safety principles. Clarifying these fallacies is critical to avoiding flawed safety architectures:

  • Misconception 1: Individual hardware components can be certified as standalone SIL systems.
    A physical device—such as a smart pressure transmitter, an emergency isolation valve, or a safety logic controller—cannot be an “SIL 3 system” on its own. Devices possess SIL capability (e.g., “SIL 3 capable”). Safety Integrity Levels apply strictly to the complete, end-to-end Safety Instrumented Function (SIF), encompassing the sensors, wiring, logic solver, final actuators, and operational proof-testing schedule. An SIL 3 capable transmitter paired with an uncertified actuator or an untested solenoid valve degrades the overall loop to SIL 1 or unrated status.
  • Misconception 2: Achieving functional safety guarantees zero equipment failures.
    Functional safety is inherently risk-based and probabilistic. It does not promise that hardware will never break or that software will never encounter an unhandled condition. Instead, it systematically reduces risk to a predetermined tolerable risk target established by industry standards and regulatory bodies. Random hardware failures are managed through statistical failure bounds ($PFD_{text{avg}}$ and $PFH$), while systematic errors are controlled through structured design lifecycles.
  • Misconception 3: Adding hardware redundancy automatically multiplies the safety integrity level.
    While redundant configurations (such as a 1oo2 dual-sensor architecture) reduce the probability of dangerous random hardware failure, they introduce vulnerability to Common Cause Failures (CCF). A common cause failure occurs when a single environmental or operational event—such as electrical power surges, ambient temperature spikes, process fluid clogging, or shared software defects—simultaneously disables all redundant channels. IEC 61508 models this vulnerability using the $beta$-factor (typically 1% to 10%). Without physical segregation, separate power routing, and diverse measurement technologies, adding identical redundant hardware yields diminishing risk-reduction returns.
  • Misconception 4: Software can be evaluated using failure rates and Mean Time Between Failures (MTBF).
    Software does not suffer from physical wear-out, chemical degradation, solder fatigue, or thermal aging. Every software failure is entirely systematic, resulting from latent logic flaws, unhandled edge cases, race conditions, or incorrect requirements. Consequently, concepts like failure rate ($lambda$) and MTBF are mathematically meaningless when applied to software. Software safety integrity is achieved exclusively through deterministic design assurance, formal requirements modeling, coding standard compliance (such as MISRA C), defensive programming, and comprehensive test coverage (such as MC/DC coverage under RTCA DO-178C and ISO 26262).
  • Misconception 5: High-reliability commercial PLCs are acceptable substitutes for certified Safety PLCs.
    Standard industrial programmable logic controllers (PLCs) are optimized for operational uptime and rapid execution, not fail-safe predictability. When an internal microcontroller register or memory bus in a standard PLC freezes, the device may hold its last output state indefinitely, keeping hazardous valves open during an emergency. Certified Safety PLCs incorporate internal dual-channel or triple-channel lockstep microprocessors, continuous internal hardware diagnostics, dynamic test pulsing on digital outputs to detect welded contacts, and fail-safe watchdog circuits that automatically de-energize outputs to a safe de-energized state upon detecting internal discrepancies.

Sources

Data: Functional Safety Integrity Levels and Cross-Sector Equivalencies

Comparative matrix of functional safety quantitative reliability targets, failure probabilities, and architectural metrics compiled from IEC 61508, ISO 26262, and SAE ARP4754A standards.

Period covered: 2010/2026. Coverage: International.

Functional Safety Integrity Levels and Cross-Sector Equivalencies
Integrity ClassificationLow-Demand PFDavg Upper Bound (probability)Continuous PFH Upper Bound (failures/h)Automotive SPFM Minimum Target (percent)Automotive LFM Minimum Target (percent)Automotive PMHF Target Ceiling (FIT)Corresponding Aviation DALAviation Failure Condition Severity
SIL 1 / ASIL A-B Entry Tier0.10.000019060100Level DMinor Failure Condition
SIL 2 / ASIL B Moderate Tier0.010.0000019060100Level CMajor Failure Condition
SIL 3 / ASIL C-D High Tier0.0011e-7978010Level BHazardous Severe-Major Condition
SIL 4 / Critical Aviation Tier0.00011e-8999010Level ACatastrophic Failure Condition

Sources

Compiled by CASRAI from the sources above. Free to reuse under CC BY 4.0 with attribution.

Follow CASRAI

Research-administration guidance, standards updates and independent tool reviews.

Ask CASRAI · full access

Ask about Functional Safety: Standards, SIL & ASIL Guide

Full access: large monthly usage, up to 10 source passages behind each answer, and MCP and API access for Claude Code, Codex and other CLIs. Cancel any time.

An AI assistant for research: funder rules, compliance, methods and publishing. It links the sources behind its answers and labels answers that come from a web search.

Answers draw on CASRAI's guides and dictionary plus the federal and funder documents we index: Federal Register, Grants.gov, Regulations.gov and UKRI.

Works on this site and inside Claude, Cursor and the AI tools you already use.

Everything CASRAI publishes — this page, the dictionary, the guides and the news — stays open to read, with no account and no card.

Referenced across the research world

University of Cambridge logoColumbia University logoCrossref logoUniversity of Edinburgh logoHarvard University logoUniversity of Oxford logoPrinceton University logoStanford School of Medicine logoUniversity College London logoORCID logoUniversity of Cambridge logoColumbia University logoCrossref logoUniversity of Edinburgh logoHarvard University logoUniversity of Oxford logoPrinceton University logoStanford School of Medicine logoUniversity College London logoORCID logo
  • University of Cambridge logo
  • Columbia University logo
  • Crossref logo
  • University of Edinburgh logo
  • Harvard University logo
  • University of Oxford logo
  • Princeton University logo
  • Stanford School of Medicine logo
  • University College London logo
  • ORCID logo

View CASRAI adoption →