Written and maintained by CASRAI Editorial Board
Published
On this page
ANSI/ASHRAE/IES Standard 90.1 is the model energy standard for buildings other than low-rise residential buildings. It is published by ASHRAE, the American Society of Heating, Refrigerating and Air-Conditioning Engineers, together with the Illuminating Engineering Society (IES), under procedures approved by the American National Standards Institute (ANSI). It sets minimum energy-efficiency requirements that a design either meets component by component or demonstrates through whole-building energy modelling. For the 2022 edition the U.S. Department of Energy (DOE) found national average site energy savings of 9.8 percent compared with the 2019 edition.
What ASHRAE Standard 90.1 is and who runs it
The full title of the edition DOE analysed is ANSI/ASHRAE/IES Standard 90.1-2022: Energy Standard for Buildings, Except Low-Rise Residential Buildings. DOE’s notice in the Federal Register states that the 2022 edition was published in January 2023, that it was developed under ANSI-approved procedures with public review and consensus, and that it is kept under continuous maintenance by an ASHRAE Standing Standard Project Committee (SSPC 90.1), which issues regular addenda between editions (Federal Register notice 2024-04717, as described on the official page on 2026-11-18).
Three separate parties are often confused. ASHRAE and IES write and publish the standard. DOE does not: the same notice says the Department neither administers nor publishes the model energy codes. DOE’s role is to evaluate each new edition against the previous one and publish a determination. States and local jurisdictions then decide what the legal energy code in their territory requires. For the competing model code that most states use for residential and many commercial buildings, see the CASRAI guide to the International Energy Conservation Code (IECC), which also covers how 90.1 sits beside it as a compliance path.
Why a research or facilities office meets 90.1
Laboratories, hospitals, teaching buildings and research offices are all commercial buildings in the standard’s sense, so their envelope, lighting, mechanical and power systems are designed against it when a jurisdiction adopts it. The DOE analysis uses 16 prototype building types, among them office, school, outpatient healthcare and hospital buildings, which together represent about 75 percent of new commercial floor area. The prototype set on the energycodes.gov prototype building models page, as described on 2026-11-18, covers 90.1-2013, 2016, 2019 and 2022 and consists of 5,168 models across 19 climate locations simulated in EnergyPlus 22.1.0 (see the CASRAI explainer on EnergyPlus building energy simulation for what such a model run involves).
What 90.1 requires: the compliance paths
DOE’s technical support document for the 2022 edition (the PNNL energy savings analysis, as described on the official page on 2026-11-18) describes the standard as offering one prescriptive route and optional whole-building performance routes. A design team picks the route; the mandatory provisions are not optional on any of them.
Prescriptive path
The prescriptive path sets component criteria, such as insulation levels, lighting power and HVAC controls, that the building must meet individually. It is the most direct route because each requirement can be checked against the drawings and specifications without an energy model.
Mandatory provisions
Some requirements in the standard are labelled mandatory. According to the technical support document, they must be met even when the design follows a performance path. A building that earns its compliance through a favourable energy model has therefore not escaped these provisions.
Energy Cost Budget (ECB) method
The ECB method is a whole-building performance path. The proposed design complies when its modelled annual energy cost is no higher than that of a reference building built to the standard’s criteria.
Performance Rating Method (PRM, Appendix G)
The Performance Rating Method in Appendix G compares the proposed design with a baseline building. The technical support document notes two features: the baseline is stable and does not tighten with each new edition, and the method gives credit for design features that the ECB method does not credit. DOE also uses Appendix G prototypes to compute building performance factors, which is the mechanism by which a percent-better-than-baseline result is related back to a specific edition. The document names a further option, the Building Envelope Trade-off Option in Appendix C.
What the 2022 edition changed
The technical support document counts 89 addenda in 90.1-2022. DOE expected 39 of them to decrease energy use, none to increase it, and 50 to have no direct impact on the modelled energy figures. Two changes are worth reading closely.
- On-site renewable energy. The 2022 edition added prescriptive requirements for on-site energy generation by renewable systems in certain building types and climate zones. The document describes this as the first time requirements for renewable energy systems have been incorporated into the prescriptive requirements of the model energy codes. Addendum “by” sets a minimum prescriptive amount of on-site renewable energy for buildings of at least 10,000 square feet.
- Scope. Addendum “cb” revises the Purpose and Scope so that the standard applies to areas outside the building that qualify under a new definition of “site”.
Because the renewable requirement changes how much energy a building draws from outside, DOE reports two kinds of result. Gross results cover efficiency only and exclude on-site generation. Net results include it. The formal determination is made on the gross, efficiency-only figure, so the headline 9.8 percent does not credit the new renewable-energy requirements.
The DOE determination and state certification
The determination is a statutory step, not a courtesy. Under section 304(b) of the Energy Conservation and Production Act (42 U.S.C. 6833(b)(2)(A)), when Standard 90.1 or a successor is revised, DOE must decide within 12 months whether the revision improves commercial building energy efficiency and publish that decision in the Federal Register. If the answer is affirmative, each State must certify within two years that it has reviewed and updated its commercial building energy code to meet or exceed the revised standard (42 U.S.C. 6833(b)(2)(B)(i)).
DOE published its determination for 90.1-2022 on 6 March 2024 (89 FR 15983). Its analysis found savings against the 2019 edition of 9.8 percent for site energy, 9.4 percent for source energy, 8.9 percent for energy cost and 9.3 percent for carbon emissions. The state certification deadline stated in the notice and on the energycodes.gov determinations page (as described on 2026-11-18) is 6 March 2026. The determinations page does not describe a determination for any later edition.
Two readings of this mechanism are common and worth avoiding. The determination does not adopt 90.1 anywhere: states choose their own code and certify that it meets or exceeds the standard. And the percentage is a national average across the prototype set, not a prediction for an individual building.
Savings by building type
The data table below, compiled from the technical support document’s Tables ES.1 to ES.3, lists each prototype building’s floor-area weight, its modelled gross site energy use intensity (EUI) under the 2019 and 2022 editions, and the percent site energy savings. The spread is wide. Strip malls and standalone retail buildings improved the most, at 19.1 and 16.0 percent. Primary schools improved the least, at 5.2 percent. Hospitals and outpatient healthcare buildings, the types most relevant to clinical research settings, fell by 7.4 and 8.8 percent, from 100.4 to 93.0 and from 99.6 to 90.8 kBtu per square foot per year.
The same table shows why a single national number should be read carefully. Quick-service restaurants have the highest absolute intensity, 469.4 kBtu per square foot per year under the 2022 edition, but a floor-area weight of only 0.3 percent, so they barely move the national average of 43.1. Warehouses carry the largest weight, 18.6 percent, and the lowest intensity, 12.8, so their 7.2 percent saving contributes substantially to the average without being large in absolute terms.
Common mistakes
- Treating a performance path as an exemption. The mandatory provisions still apply when compliance is shown by modelling.
- Expecting the Appendix G baseline to move with each edition. The baseline is stable, so a “percent better than 90.1” claim is meaningful only with the edition and the method named.
- Quoting 9.8 percent as the saving for a specific building. It is a national, floor-area-weighted average of prototype results; the table shows building types ranging from 5.2 to 19.1 percent.
- Reading the determination as adoption. DOE evaluates the edition; each State certifies its own code, and DOE does not write the codes.
- Mixing gross and net figures. The determination rests on efficiency-only (gross) results, while the on-site renewable requirement is reported separately as a net impact.
- Citing an addendum-era requirement as part of the published edition, or the reverse. The standard is under continuous maintenance, so confirm which edition and which addenda your jurisdiction has adopted.
Typical project phases
- Identify which edition of 90.1, or which alternative such as the IECC, the jurisdiction has adopted for the building type.
- Choose the route: prescriptive, ECB or Appendix G performance rating.
- For performance routes, build the proposed and reference or baseline models and confirm the mandatory provisions separately.
- Document the result for the code official in the form the jurisdiction requires.
Related standards and CASRAI guides
| Standard or tool | What the CASRAI guide covers |
|---|---|
| IECC | Model energy rules, compliance pathways, DOE determinations and research facility standards |
| ASHRAE 170 | The room-by-room air-change-rate and pressure-relationship table for operating rooms, isolation rooms and sterile processing |
| ASHRAE 110 | The fume hood test method: face velocity, smoke visualisation and tracer-gas containment |
| EnergyPlus | The building energy simulation program DOE uses for its 90.1 prototype models |
Standard 90.1 concerns energy efficiency. Ventilation rates for healthcare spaces and fume hood performance are set by other ASHRAE documents, which is why a laboratory or hospital project normally has to reconcile several standards at once.
Sources
- Federal Register: Determination Regarding Energy Efficiency Improvements in ANSI/ASHRAE/IES Standard 90.1-2022 (89 FR 15983), checked 2026-11-18
- U.S. Department of Energy (PNNL): ANSI/ASHRAE/IES Standard 90.1-2022 Energy Savings Analysis, technical support document, checked 2026-11-18
- U.S. DOE Building Energy Codes Program: Commercial determinations, checked 2026-11-18
- U.S. DOE Building Energy Codes Program: Prototype building models, checked 2026-11-18
Data: Standard 90.1-2019 vs 90.1-2022: modelled gross site energy use intensity by prototype building type
Per-prototype-building gross site energy use intensity (efficiency only, excluding on-site generation) under the 2019 and 2022 editions of ANSI/ASHRAE/IES Standard 90.1, with floor-area weights and percent savings, compiled from DOE's technical support document Tables ES.1 to ES.3.
Period covered: 2019/2022 editions. Coverage: United States.
| Prototype building type | Floor-area weight (%) | Site EUI, 90.1-2019 (kBtu/ft2-yr) | Site EUI, 90.1-2022 (kBtu/ft2-yr) | Site energy savings (%) |
|---|---|---|---|---|
| Small Office | 3.8 | 28.2 | 25.7 | 8.9 |
| Medium Office | 5 | 30.8 | 27.5 | 10.7 |
| Large Office | 3.9 | 53.9 | 50.2 | 6.9 |
| Standalone Retail | 10.9 | 46.8 | 39.3 | 16 |
| Strip Mall | 3.7 | 50.2 | 40.6 | 19.1 |
| Primary School | 4.8 | 43.9 | 41.6 | 5.2 |
| Secondary School | 10.9 | 39.1 | 36.4 | 6.9 |
| Outpatient Healthcare | 3.4 | 99.6 | 90.8 | 8.8 |
| Hospital | 4.5 | 100.4 | 93 | 7.4 |
| Small Hotel | 1.6 | 61.3 | 53.9 | 12.1 |
| Large Hotel | 4.2 | 84.4 | 75 | 11.1 |
| Warehouse | 18.6 | 13.8 | 12.8 | 7.2 |
| Quick-Service Restaurant | 0.3 | 502.2 | 469.4 | 6.5 |
| Full-Service Restaurant | 1 | 341.5 | 316.5 | 7.3 |
| Mid-Rise Apartment | 13.7 | 39.3 | 35.5 | 9.7 |
| High-Rise Apartment | 9.6 | 45.3 | 40 | 11.7 |
| National weighted average | 100 | 47.8 | 43.1 | 9.8 |
Sources
- DOE/PNNL: ANSI/ASHRAE/IES Standard 90.1-2022 Energy Savings Analysis (Tables ES.1-ES.3) (accessed 2026-11-18)
Compiled by CASRAI from the sources above. Free to reuse under CC BY 4.0 with attribution.