Ten States Standards: What They Are, Editions and Lab Requirements

What the Ten States Standards (GLUMRB Recommended Standards) are, the editions in circulation, and the laboratory requirements in Section 58.

Written and maintained by CASRAI Editorial Board

Published

On this page

The Ten States Standards are the common name for the “Recommended Standards” documents published by the Great Lakes – Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers (GLUMRB). They are design guides, not statutes: reviewing authorities in the member states and in Ontario use them to evaluate plans and specifications for water works and wastewater facilities. The wastewater volume also sets out what a treatment-plant laboratory must contain.

Definition and scope

The wastewater volume’s formal title is Recommended Standards for Wastewater Facilities: Policies for the Design, Review, and Approval of Plans and Specifications for Wastewater Collection and Treatment Facilities. The 2014 edition names the following as member states and province on its cover: Illinois, Indiana, Iowa, Michigan, Minnesota, Missouri, New York, Ohio, Ontario, Pennsylvania and Wisconsin. That is ten states plus Ontario, which is why the “ten” in the name undercounts the membership. The foreword says Ontario was invited as a Great Lakes participant in 1977.

The Minnesota Department of Health describes the standards as “intended to serve as a guide in the design and preparation of plans and specifications”. The Iowa Department of Natural Resources says they are “commonly referred to as the Ten States Standards”, that they are referenced in state rules, and that Iowa DNR uses them to supplement Iowa’s own Wastewater Facilities Design Standards.

The 2014 foreword limits the scope: the standards are for “normal situations” and for more conventional municipal wastewater collection and treatment systems. Innovative approaches, especially very small systems, are not covered, and the designer is told to contact the reviewing authority. The foreword also states that a missing description or criterion for a unit process or piece of equipment does not mean it should not be used; such items are evaluated on the information submitted.

How reviewing authorities use them

According to the 2014 foreword, the document’s aim is to suggest limiting values that a reviewing authority can use when it evaluates plans, and to encourage uniformity of practice among the states and the province. Two points from the foreword explain why the document cannot be treated as one national or regional rule book:

  • Statutory requirements, regulations and guidelines are not uniform among the member states and the province, so users must be aware of local rules and of federal requirements.
  • The wording carries weight. “Shall” marks a provision sufficiently standardized, or important enough for public health or water quality, to be treated as a requirement of the standards. “Should”, “recommended” and “preferred” mark desirable practice, and deviations are subject to individual consideration by the reviewing authority.

In practice, then, an engineer or a laboratory planner reads the standards together with the state or provincial rules that apply to the project. A “shall” in the standards still has to be reconciled with how that jurisdiction adopts or references the document.

Editions and companion standards

The 2014 foreword records the history: a Committee on Development of Uniform Standards for Sewage Works was created in 1947, the first standards were published in 1951, and the wastewater volume was revised in 1960, 1968, 1971, 1973, 1978, 1990, 1997, 2004 and 2014. The Minnesota Department of Health page (last updated 22 June 2026, read 12 November 2026) lists the current and archived documents, summarized in the table below.

The same page lists a 2026 edition of the wastewater standards as the current wastewater book, available as a download. This guide describes the contents of the 2014 edition only, because that is the edition whose text was read for it. Iowa DNR’s design standards page still points to the 2014 edition. Confirm which edition your reviewing authority has adopted before relying on any section number or value quoted below.

Document (GLUMRB) Listing on the Minnesota Department of Health page
Standards for Water Works, 2022 Edition Current
Recommended Standards for Wastewater Facilities, 2026 Current (book, download only)
Standards for Water Works, 2012 and 2007 editions Archived
Recommended Standards for Wastewater Facilities, 2014 Edition Archived
Recommended Standards for Bathing Beaches, 1990 Archived
Recommended Standards for Individual Sewage Systems, 1980 Archived

Chapter map of the 2014 wastewater edition

The 2014 edition is organized in numbered chapters, each starting at a multiple of ten. Section numbers inside a chapter run from that base, so Section 58 sits inside Chapter 50.

Chapter Title in the 2014 edition
10 Engineering Reports and Facility Plans
20 Engineering Plans and Specifications
30 Design of Sewers
40 Wastewater Pumping Stations
50 Wastewater Treatment Facilities
60 Screening, Grit Removal, and Flow Equalization
70 Settling
80 Sludge Processing, Storage, and Disposal
90 Biological Treatment
100 Disinfection
110 Supplemental Treatment Processes

The laboratory requirement in Section 58

For readers who run or equip a laboratory, Section 58 of the 2014 wastewater edition is the part that matters. Its first paragraph, 58.1, says all treatment plants “shall include a laboratory for making the necessary analytical determinations and operating control tests”. The exception is a plant that uses only processes not requiring laboratory testing for plant control and that has satisfactory off-site laboratory provisions to meet its permit monitoring requirements. The laboratory must have sufficient size, bench space, equipment and supplies to carry out all self-monitoring analytical work required by discharge permits and the process control tests needed for each treatment process in the design.

Section 58.1 adds that the laboratory should be flexible enough to allow future expansion, and that its size and instrumentation should reflect plant size, staffing, process complexity and applicable certification requirements. It then sorts plant laboratories into three categories by the testing performed. The data table below the guide compares what Sections 58.2 to 58.4 say for each category.

Category I: basic operational testing

Category I covers plants performing only basic operational testing, which the standards say typically includes pH, temperature and dissolved oxygen. Section 58.2 says a floor area up to 150 square feet (14 m2) should be adequate, preferably at the treatment site. It requires electricity, water, heat, sufficient storage space, a sink and a bench top, and says components need not be industrial grade. Equipment and glassware shall be of the types recommended by Standard Methods for the Examination of Water and Wastewater and the reviewing authority.

Category II: operational and permit testing

Category II covers plants performing more complex operational and permit tests, including biochemical oxygen demand, suspended solids and bacterial analysis. Section 58.3 says these laboratories should generally provide a minimum of approximately 300 square feet (28 m2), with adequate bench space for each analyst, and that floors should be fire resistant and highly resistant to acids, alkalies, solvents and salts. Fume hoods shall be provided where the analytical work produces noxious fumes, and a laboratory-grade sink and drain trap shall be provided. An analytical balance of the automatic, digital readout, single pan, 0.1 milligram sensitivity type shall be provided, preferably on a heavy balance table set away from windows, doors and drafts. Reagent water of a purity suitable for the analyses shall be supplied; the text notes that water from an all-glass distillation system is generally adequate but some analyses require deionization.

The safety provisions are specific. Laboratories shall have first aid equipment, protective clothing including goggles, gloves and aprons, and a fire extinguisher. Eyewash fountains and safety showers on potable water shall be no more than 25 feet (7.6 m) from points of hazardous chemical exposure. An eyewash is to be supplied with water at 50 to 90 °F (10 to 32 °C), suitable for 15 to 30 minutes of continuous irrigation, and a shower shall be capable of at least 20 gpm (1.3 L/s).

Category III: complex, pretreatment and multi-plant testing

Category III adds industrial pretreatment and multiple-plant testing. Section 58.4 gives no fixed floor area. It says space and layout should follow an evaluation of the complexity, volume and variety of analyses expected over the plant’s design life, and that the needs should be described in the engineering report or facility plan. For less complicated needs, bench-top working surface should occupy at least 35 percent of the laboratory floor space. Separate and possibly isolated areas shall be considered for special equipment, glassware and chemical storage, sample storage areas shall have adequate security, and provisions for storing and disposing of chemical wastes shall be made. Its safety list is longer than Category II: it adds full face shields, chemical spill kits, “No Smoking” signs in hazardous areas and warning signs for slippery areas, non-potable water fixtures and chemical and fuel storage. A binocular or trinocular phase contrast microscope is recommended for process control at activated sludge plants, and natural or LP gas, not digester gas, should be supplied.

Laboratory staff will recognize the overlap with their own controls. Written methods and records for these tests fall under the plant’s standard operating procedures, and a plant that also works under a quality regime may compare Section 58 with good laboratory practice expectations. Section 58 itself refers readers to Standard Methods and the U.S. EPA Analytical Procedures Manual when specifying equipment. For a sample-based indicator measured in such laboratories, see the guide to fecal coliform testing, and for the engineering field around these facilities see what environmental engineering is.

Common misunderstandings

“The Ten States Standards are a law.”

They are a design guide for plan review. The foreword states that statutory requirements differ among the jurisdictions, and Iowa DNR describes using them to supplement its own rules. Whether a provision binds a given project depends on how that state or province references the document.

“Only ten states are involved.”

The cover of the 2014 edition lists eleven members: ten states and Ontario.

“If a process is not described, it is not allowed.”

The foreword says the opposite: absence of a description or criterion does not suggest a process or equipment should not be used, and it is evaluated on the information submitted.

“There is a single Ten States Standards book.”

There are separate GLUMRB documents for water works and wastewater facilities, plus archived volumes on bathing beaches and individual sewage systems. The wastewater and water works books are on different edition cycles.

“Section 58 applies to every laboratory.”

It applies to treatment plant laboratories reviewed under the wastewater standards. It is not a general laboratory design code, and the three categories are described as expected minimum needs that may be increased for industrial monitoring or special process requirements.

FAQ

What are the Ten States Standards?

They are the Recommended Standards documents of the Great Lakes – Upper Mississippi River Board of State and Provincial Public Health and Environmental Managers, used by reviewing authorities as a guide for evaluating water works and wastewater facility plans.

Who publishes them?

GLUMRB. The 2014 wastewater edition was published by Health Research, Inc. in Albany, New York, with copyright held by the Board; the document may be reproduced if credit is given to the Board and the publication.

Which edition is current?

As of the Minnesota Department of Health page updated 22 June 2026, the current listings are Standards for Water Works 2022 and Recommended Standards for Wastewater Facilities 2026. Iowa DNR’s page still cites the 2014 wastewater edition, so check what your reviewing authority uses.

Do the standards require a plant laboratory?

The 2014 edition, Section 58.1, says all treatment plants shall include a laboratory, with an exception for plants using only processes that need no laboratory testing for control and that have satisfactory off-site laboratory provisions.

Sources

  • GLUMRB, Recommended Standards for Wastewater Facilities, 2014 Edition (PDF hosted by the Minnesota Department of Health), health.mn.gov, read 12 November 2026.
  • Minnesota Department of Health, Ten States Standards page, health.mn.gov, last updated 22 June 2026, read 12 November 2026.
  • Iowa Department of Natural Resources, Wastewater Design Standards, iowadnr.gov, read 12 November 2026.

Data: Ten States Standards (2014 wastewater edition): treatment plant laboratory provisions by category

Compares what Sections 58.2, 58.3 and 58.4 of the GLUMRB Recommended Standards for Wastewater Facilities (2014 Edition) say about space, balance, fume hoods and eyewash provisions for the three plant laboratory categories. Compiled by reading the standards text directly; 'not specified' means the section is silent.

Period covered: 2014. Coverage: Illinois, Indiana, Iowa, Michigan, Minnesota, Missouri, New York, Ohio, Ontario, Pennsylvania, Wisconsin.

Ten States Standards (2014 wastewater edition): treatment plant laboratory provisions by category
Laboratory categoryTypical testing (Section 58.1)Floor space guidanceAnalytical balanceFume hoodsEyewash and safety shower
Category I (Section 58.2)Basic operational testing, typically pH, temperature, dissolved oxygenUp to 150 sq ft (14 m2) should be adequateNot specified in 58.2Not specified in 58.2Not specified in 58.2
Category II (Section 58.3)Operational and permit tests including BOD, suspended solids, bacterial analysisMinimum approx. 300 sq ft (28 m2); adequate bench space for each analystShall be provided: automatic digital single pan, 0.1 mg sensitivityShall be provided where work produces noxious fumesShall be provided; no more than 25 ft (7.6 m) from hazardous chemical exposure
Category III (Section 58.4)Operational, permit, industrial pretreatment and multiple plant testingNo fixed area; based on evaluation of complexity, volume and variety of analyses; bench top at least 35 percent of floor for less complicated needsShall be provided: automatic digital single pan, 0.1 mg sensitivityShall be provided where work produces noxious fumes; canopy hoods over heat-releasing equipmentShall be provided; no more than 25 ft (7.6 m) from hazardous chemical exposure

Sources

Compiled by CASRAI from the sources above. Free to reuse under CC BY 4.0 with attribution.

Follow CASRAI

Research-administration guidance, standards updates and independent tool reviews.

Ask CASRAI · full access

Ask about Ten States Standards: What They Are, Editions and Lab Requirements

Full access: large monthly usage, up to 10 source passages behind each answer, and MCP and API access for Claude Code, Codex and other CLIs. Cancel any time.

An AI assistant for research: funder rules, compliance, methods and publishing. It links the sources behind its answers and labels answers that come from a web search.

Answers draw on CASRAI's guides and dictionary plus the federal and funder documents we index: Federal Register, Grants.gov, Regulations.gov and UKRI.

Works on this site and inside Claude, Cursor and the AI tools you already use.

Everything CASRAI publishes — this page, the dictionary, the guides and the news — stays open to read, with no account and no card.

Referenced across the research world

University of Cambridge logoColumbia University logoCrossref logoUniversity of Edinburgh logoHarvard University logoUniversity of Oxford logoPrinceton University logoStanford School of Medicine logoUniversity College London logoORCID logoUniversity of Cambridge logoColumbia University logoCrossref logoUniversity of Edinburgh logoHarvard University logoUniversity of Oxford logoPrinceton University logoStanford School of Medicine logoUniversity College London logoORCID logo
  • University of Cambridge logo
  • Columbia University logo
  • Crossref logo
  • University of Edinburgh logo
  • Harvard University logo
  • University of Oxford logo
  • Princeton University logo
  • Stanford School of Medicine logo
  • University College London logo
  • ORCID logo

View CASRAI adoption →