Skip to main content
v2026.11,986 entries · CC-BY 4.0
LAC HealthSponsored

Shop hepa filter supplies

  • FDA registered
  • ISO 13485
  • BBB Accredited A+

Shop at LAC Health

HEPA Filter Sizes: Standard Dimensions & Sizing Chart

A comprehensive engineering reference for HEPA filter sizes, comparing nominal vs. actual dimensions, airflow CFM ratings, and cleanroom frame specifications.

Written and maintained by CASRAI Editorial Board

Published

On this page

Standard HEPA filter sizes range from compact 8 in × 8 in modules used in specialized containment housings up to standard 24 in × 24 in and 24 in × 72 in units deployed across cleanrooms, laminar flow benches, and laboratory HVAC plenums. In technical air filtration, selecting the correct HEPA filter requires distinguishing between rounded nominal sizes used in catalog descriptions and exact actual dimensions milled with tight negative tolerances (typically −1/8 in or −1/16 in to +0 in) to ensure leak-tight compression against mounting gaskets or fluid gel seals. Airflow capacity scales directly with face area and media pack depth, with standard deep-pleat box filters operating at 250 to 500 feet per minute (FPM) face velocity, while cleanroom mini-pleat panels are engineered for 90 ± 20 FPM unidirectional laminar flow.

Standard HEPA Filter Sizing Chart

The standard lookup table below compiles open-face rectangular HEPA filter designations defined in ASME AG-1 (Section FC, Table FC-4110) and U.S. Department of Energy standard DOE-STD-3020-2015. These standardized industrial sizes (Sizes 1 through 9) govern critical containment, nuclear air-cleaning housings, and heavy-duty laboratory filtration banks.

Standard Designation Nominal Dimensions (H × W × D, in) Actual Dimensions (H × W × D, mm) Rated Airflow (ACFM) Rated Airflow (m³/h) Max Clean Resistance (in. wg) Max Clean Resistance (Pa) Typical Lab & Facility Application
Size 1 8 × 8 × 3 1/16 203 × 203 × 78 25 42 1.3 325 Glovebox exhaust, analytical instrument sampling lines
Size 2 8 × 8 × 5 7/8 203 × 203 × 149 50 85 1.3 325 Small containment enclosures, radioactive tracer hoods
Size 3 8 × 24 × 5 7/8 203 × 610 × 149 150 255 1.3 325 Narrow duct runs, low-profile in-line filter housings
Size 4 12 × 12 × 5 7/8 305 × 305 × 149 100 170 1.3 325 Mini-environments, pass-through boxes, local exhausts
Size 5 24 × 24 × 5 7/8 610 × 610 × 149 500 850 1.0 250 Medium-capacity supply banks, pharmaceutical prep suites
Size 6 12 × 24 × 11 1/2 305 × 610 × 292 500 850 1.0 250 Vertical clean benches, modular HVAC side-access housings
Size 7 24 × 24 × 11 1/2 610 × 610 × 292 1,000 1,700 1.0 250 Standard air-handling unit (AHU) final filtration banks
Size 8 (High Capacity) 24 × 24 × 11 1/2 610 × 610 × 292 2,000 3,400 1.3 325 High-velocity central ventilation, high-throughput containment
Size 9 24 × 30 × 11 1/2 610 × 762 × 292 1,250 2,125 1.3 325 Large containment plenums, industrial processing exhaust

Always check your product’s labelling and the manufacturer’s certified cut sheet before ordering replacement filters, as individual housing frames require specific gasket placements or knife-edge clearances.

How to Read HEPA Filter Dimensions: Nominal vs. Actual Size

A frequent point of confusion when replacing high-efficiency particulate air filters is the gap between nominal and actual dimensions. The nominal dimension is an abbreviated commercial label rounded to the nearest whole inch (such as 24 in × 24 in × 11 1/2 in). The actual dimension is the physical measurement of the outer casing, measured edge-to-edge across the outer flange or frame walls with a calibrated rule.

In standard gasketed industrial housings conforming to ASME AG-1 and DOE-STD-3020, filter frames are fabricated with strict negative tolerances so that units slide freely into mounting racks without binding. Per DOE-STD-3020 Table 5-2, filters with face dimensions under 24 in carry a standard tolerance of −1/16 in to +0 in (−1.6 mm to +0 mm). For filters with face dimensions of 24 in or larger, allowable tolerance is −1/8 in to +0 in (−3.2 mm to +0 mm). Frame depth carries a tolerance of ±1/16 in (±1.6 mm). Consequently, a nominal 24 in × 24 in filter measures 23 7/8 in × 23 7/8 in or 23 3/8 in × 23 3/8 in depending on frame design.

Cleanroom ceiling grid modules and terminal fan-filter units (FFUs) follow a distinct sizing convention governed by cleanroom architectural standards such as IEST-RP-CC001. A standard cleanroom ceiling grid is laid out on 2 ft × 4 ft (24 in × 48 in) or 2 ft × 2 ft (24 in × 24 in) centerlines. Because the inverted T-bar grid extrusion occupies 1 in to 1 1/2 in of flange width, an actual filter face dimension must be undercut to sit squarely on the grid gasket or into the fluid seal trough. For a nominal 24 in × 48 in grid opening, the actual physical filter frame typically measures 23 5/8 in × 47 5/8 in (600 mm × 1210 mm). Placing an un-milled 24 in × 48 in frame into a cleanroom grid results in frame overlap, broken seal planes, and severe aerosol bypass.

When recording filter dimensions from an existing installation, technicians must document four parameters:

  • Outer Frame Face Dimensions: Outside width and height of the rigid casing, excluding gasket material.
  • Total Depth: Depth of the outer frame casing (typically 2 in, 2 3/4 in, 3 1/16 in, 5 7/8 in, or 11 1/2 in).
  • Gasket Location and Thickness: Whether the gasket is positioned upstream, downstream, on both faces, or along the side perimeter. Standard closed-cell neoprene gaskets add 1/4 in (6.35 mm) of uncompressed thickness.
  • Gel Channel Dimensions: For knife-edge fluid seals, measure the channel width, depth, and centerline location to ensure proper engagement with the housing blade.

How to Measure and Calculate the Correct HEPA Filter Size

Sizing a HEPA filter for a laboratory clean bench, biosafety cabinet, or cleanroom plenum involves calculating volumetric airflow, allowable face velocity, and resulting media surface area. In critical equipment like a laminar flow hood, air must sweep across the work surface in uniform parallel streamlines without inducing turbulence that could entrain room contaminants.

Airflow Sizing Formula

The relationship between volumetric airflow rate, face velocity, and filter face area is governed by the continuity equation:

$$Q = V imes A$$

Where:

  • Q: Volumetric airflow rate in cubic feet per minute (CFM) or cubic meters per hour (m³/h).
  • V: Design face velocity in feet per minute (FPM) or meters per second (m/s).
  • A: Net active face area of the filter in square feet (ft²) or square meters (m²).

Laminar Flow Bench Sizing Calculation

Consider an engineering team sizing a filter for a 4-foot horizontal laminar flow clean bench. The work zone measures 46 inches wide by 22 inches high. Cleanroom guidelines mandate an average laminar face velocity of 90 FPM ± 20 FPM (0.45 m/s ± 0.1 m/s) across the active work zone.

  1. Calculate Face Area ($A$): Width = 46 in / 12 = 3.833 ft; Height = 22 in / 12 = 1.833 ft.

    $$A = 3.833 ext{ ft} imes 1.833 ext{ ft} = 7.026 ext{ sq ft}$$

  2. Calculate Required Airflow ($Q$):

    $$Q = 90 ext{ FPM} imes 7.026 ext{ sq ft} = 632.3 ext{ CFM}$$

  3. Select Filter Size and Depth: A nominal 24 in × 48 in mini-pleat panel filter provides 8.0 sq ft gross area, yielding approximately 7.1 sq ft net active media area once frame margins are subtracted. Operating 632 CFM across 7.1 sq ft yields an actual face velocity of $V = 632.3 / 7.1 pprox 89.1 ext{ FPM}$, delivering an initial clean resistance of 0.45 in. wg to 0.52 in. wg (112 to 130 Pa).

Biosafety Cabinet Filter Sizing

In Class II biosafety cabinets, two separate HEPA filters must be sized to maintain containment: the downflow (supply) filter and the exhaust filter. For a detailed comparison of biological safety cabinets versus non-containment hoods, refer to our analysis of biosafety cabinets vs. laminar flow hoods.

In a standard 4-foot Class II Type A2 cabinet conforming to NSF/ANSI Standard 49, the downflow filter spans the full width of the upper plenum to deliver 50 to 60 FPM laminar downflow over the work surface. The standard supply HEPA filter measures nominally 18 in × 48 in × 3 1/16 in (actual dimensions approximately 18.0 in × 48.0 in × 3.06 in / 457 mm × 1219 mm × 78 mm). The exhaust filter discharges filtered air into the room or an external canopy duct, handling roughly 30% of total circulating air. Standard exhaust filters for 4-foot cabinets measure 18 in × 24 in × 11 1/2 in (or 18 in × 18 in × 5 7/8 in in low-profile designs). In a 6-foot Class II cabinet, the supply filter expands to 18 in × 72 in × 3 1/16 in, paired with an 18 in × 30 in × 11 1/2 in exhaust unit.

When validating containment ventilation systems during commissioning, teams should follow structured IQ/OQ/PQ protocols to document that installed filter dimensions, seating tolerances, and airflow velocities meet engineering specifications.

Equivalence Notes: Airflow Velocity, Depth, and Media Construction

HEPA filter sizing cannot be evaluated solely on outer face dimensions; media pack geometry and pleating technology dictate airflow capacity, static pressure drop, and service life.

Deep-Pleat vs. Mini-Pleat Construction

HEPA filters are manufactured using two primary pleating configurations:

  • Deep-Pleat (Separator) Filters: Traditional construction utilizes pleats extending 5 7/8 in to 11 1/2 in deep. Continuous sheets of borosilicate glass micro-fiber paper are folded over corrugated aluminum separators. The corrugated separators support the media folds and maintain open air channels. An 11 1/2-inch deep Size 7 filter accommodates over 200 sq ft of filter media inside a 24 in × 24 in face footprint, permitting high-velocity turbulent flow (250 to 500 FPM) at an initial pressure drop of 1.0 in. wg (250 Pa).
  • Mini-Pleat (Separatorless) Filters: Modern cleanroom and cabinet HEPA filters utilize shallow pleat packs ranging from 2 in to 4 in in depth. Instead of corrugated aluminum separators, mini-pleat packs use thin ribbons of synthetic hot-melt adhesive beads spaced 1/2 in to 1 in apart. Mini-pleat construction reduces filter weight by 40% to 60% and slashes frame depth, making it ideal for ceiling fan-filter units and laminar flow benches. However, because mini-pleat panels have less total media surface area than deep-pleat boxes, they operate at lower face velocities (70 to 120 FPM) to avoid excessive static resistance.

Standards Equivalence: US vs. International Ratings

Cross-referencing HEPA filter specifications across multinational lab facilities requires mapping US military and IEST standards to European and ISO frameworks. While US standards historically tested at a single fixed particle diameter (0.3 µm aerosol), EN 1822 and ISO 29463 evaluate filters at the Most Penetrating Particle Size (MPPS), typically between 0.12 µm and 0.25 µm.

US Standard (MIL-STD-282 / IEST-RP-CC001) Rated Efficiency (at 0.3 µm) European Standard (EN 1822:2019) International Standard (ISO 29463) MPPS Integral Efficiency (%) MPPS Local Penetration Limit (%)
Type A (Standard Industrial) 99.97% E12 ISO 25 E / 30 E ≥ 99.5% No scan test required
Type C (Scan Tested) 99.99% H13 ISO 35 H ≥ 99.95% ≤ 0.25%
Type D (Zero-Leak Precision) 99.99% H14 ISO 45 H ≥ 99.995% ≤ 0.025%
Type F (ULPA Grade) 99.999% U15 ISO 55 U ≥ 99.9995% ≤ 0.0025%

For cleanroom compounding operations and hazardous drug containment, facilities must ensure installed filter grades and housing depths comply with strict regulatory frameworks, such as USP 800 cleanroom requirements for negative-pressure buffer areas.

Common HEPA Filter Sizing and Installation Mix-Ups

Dimensional errors during filter procurement create facility downtime, aerosol bypass leaks, or blower motor overload. Technical staff frequently encounter the following installation pitfalls:

  • Mismatched Gasket vs. Gel Seals: Placing a gasket-seal HEPA filter into a knife-edge gel grid (or vice versa) causes immediate bypass. A gasket-seal filter features a flat closed-cell neoprene perimeter designed for mechanical compression against a flat housing flange. A gel-seal filter features a perimeter trough filled with silicone or polyurethane gel that mates with a downward knife-edge blade. Attempting to clamp a gel-seal filter into a mechanical frame damages the gel trough and allows particulate bypass around the casing.
  • Assuming Nominal Dimensions Match Frame Openings: Ordering a 24 in × 48 in filter for a 24 in × 48 in ceiling module without verifying actual manufacturing undercuts results in units that physically cannot fit between T-bar ribs. Always measure the clear interior opening of the holding frame and verify whether the existing filter is 23 5/8 in, 23 1/4 in, or 24 0/0 in wide.
  • Exchanging Deep-Pleat for Shallow Mini-Pleat Without Blower Re-Balancing: Swapping an 11 1/2-inch deep-pleat box filter for a 3-inch mini-pleat panel inside a high-volume HVAC duct dramatically increases media face velocity, causing static resistance to spike rapidly and overloading the supply blower.
  • Ignoring Pre-Filter Stage Depths: HEPA filters are final polishing stages, not particulate bulk collectors. Installing an oversized HEPA filter that eliminates the physical space reserved for 2-inch or 4-inch pre-filters leads to rapid dust loading, surface blinding, and premature filter failure.
  • Over-Compressing Mechanical Gaskets: When tightening holding clamps on mechanical gasketed frames, over-torquing crushes the closed-cell neoprene beyond its 50% elastic limit, inducing permanent frame racking and creating hairline corner leaks that fail DOP/PAO aerosol challenge tests.

Frequently Asked Questions

What is the difference between nominal and actual HEPA filter dimensions?

Nominal dimensions are rounded commercial labels (such as 24 in × 24 in × 12 in) describing general equipment classes. Actual dimensions are the exact physical outside casing measurements (such as 23 3/8 in × 23 3/8 in × 11 1/2 in). Housings require negative dimensional tolerances so filters seat properly against compression gaskets or gel channels without binding.

What are the standard HEPA filter sizes for a 4-foot biosafety cabinet?

A standard 4-foot Class II biosafety cabinet typically uses an 18 in × 48 in × 3 1/16 in downflow supply filter and an 18 in × 24 in × 11 1/2 in exhaust filter (or 18 in × 18 in × 5 7/8 in on compact models). Always check the cabinet’s serial number and technical manual before ordering replacements.

Why are cleanroom ceiling HEPA filters manufactured at 23 5/8 inches instead of 24 inches?

Ceiling T-bar grids are laid out on 24-inch centerlines. Because the structural T-bar extrusion occupies physical flange width, a true 24-inch casing would bind against the grid ribs. HEPA panels are manufactured at 23 5/8 inches (or 600 mm) to seat squarely into grid gaskets or knife-edge gel troughs.

What face velocity should be used when sizing a laminar flow hood HEPA filter?

Standard laboratory clean benches and laminar flow hoods are engineered for an average air velocity of 90 FPM ± 20 FPM (0.45 m/s ± 0.1 m/s). Lower velocities risk room air backwashing into the cabinet, while higher velocities create turbulence that can compromise sample protection.

Can a deep-pleat HEPA filter be replaced with a mini-pleat filter?

Only if the ventilation system’s airflow produces an acceptable face velocity across the mini-pleat face area and transition blanking plates are fitted. Mini-pleat panels have less total media surface area than 11 1/2-inch deep-pleat boxes, causing rapid pressure rise if airflow is not properly balanced.

How does HEPA filter depth affect static pressure drop and service life?

Deeper filters contain more media surface area within the same face footprint. An 11 1/2-inch deep-pleat filter packs over 200 sq ft of media into a 24 in × 24 in frame, maintaining low media velocity, reducing initial resistance to 1.0 in. wg (250 Pa), and extending filter lifespan up to 3 to 5 years.

Sources

Data: Cleanroom and Laboratory Biosafety Cabinet HEPA Filter Specifications

Cross-manufacturer technical specifications comparing nominal dimensions, actual physical casing dimensions, media pack depth, rated laminar airflow capacity, face velocity, clean initial resistance, and frame seal configurations for cleanroom ceiling modules and Class II biosafety cabinets. Compiled from IEST-RP-CC001.7, NSF/ANSI 49, Camfil Megalam data sheets, and Labconco engineering manuals.

Period covered: 2024/2026. Coverage: Global.

Cleanroom and Laboratory Biosafety Cabinet HEPA Filter Specifications
Equipment and Filter ApplicationNominal Width (in)Nominal Height (in)Nominal Depth (in)Actual Width (in)Actual Height (in)Actual Depth (in)Rated Airflow (CFM)Face Velocity (FPM)Initial Resistance (in. wg)Frame Seal Type
Cleanroom Ceiling FFU Module 2x22424323.62523.6252.75450900.45Knife-Edge Gel Seal
Cleanroom Ceiling FFU Module 2x42448323.62547.6252.75900900.45Knife-Edge Gel Seal
Cleanroom Terminal Panel 2x2 (Gasket)24245.87523.62523.6255.8755001000.52Neoprene Compression Gasket
Cleanroom Terminal Panel 2x4 (Gasket)24485.87523.62547.6255.87510001000.52Neoprene Compression Gasket
Class II BSC 3-Foot Supply Downflow18363.0618363.06350550.48Knife-Edge Gel Seal
Class II BSC 3-Foot Exhaust Filter18185.8818185.88180800.65Neoprene Compression Gasket
Class II BSC 4-Foot Supply Downflow18483.0618483.06475550.48Knife-Edge Gel Seal
Class II BSC 4-Foot Exhaust Filter182411.5182411.5290950.58Neoprene Compression Gasket
Class II BSC 6-Foot Supply Downflow18723.0618723.06710550.48Knife-Edge Gel Seal
Class II BSC 6-Foot Exhaust Filter183011.5183011.5435950.58Neoprene Compression Gasket

Sources

Compiled by CASRAI from the sources above. Free to reuse under CC BY 4.0 with attribution.

Follow CASRAI

Research-administration guidance, standards updates and independent tool reviews.

Ask CASRAI · free to try

Ask about HEPA Filter Sizes: Standard Dimensions & Sizing Chart

2 free questions a day, no account.

An AI assistant for research: funder rules, compliance, methods and publishing. It links the sources behind its answers and labels answers that come from a web search.

Answers draw on CASRAI's guides and dictionary plus the federal and funder documents we index: Federal Register, Grants.gov, Regulations.gov and UKRI.

Works on this site and inside Claude, Cursor and the AI tools you already use.

Everything CASRAI publishes — this page, the dictionary, the guides and the news — stays open to read, with no account and no card.

Referenced across the research world

University of Cambridge logoColumbia University logoCrossref logoUniversity of Edinburgh logoHarvard University logoUniversity of Oxford logoPrinceton University logoStanford School of Medicine logoUniversity College London logoORCID logoUniversity of Cambridge logoColumbia University logoCrossref logoUniversity of Edinburgh logoHarvard University logoUniversity of Oxford logoPrinceton University logoStanford School of Medicine logoUniversity College London logoORCID logo
  • University of Cambridge logo
  • Columbia University logo
  • Crossref logo
  • University of Edinburgh logo
  • Harvard University logo
  • University of Oxford logo
  • Princeton University logo
  • Stanford School of Medicine logo
  • University College London logo
  • ORCID logo

View CASRAI adoption →