Written and maintained by CASRAI Editorial Board
Published · Last updated
On this page
OSHA has no general secondary containment rule for chemical storage. Its numeric containment provisions sit in 29 CFR 1910.106 and cover diked flammable liquid tanks, outdoor containers and inside storage rooms. The “10% or the largest container” formula is an EPA hazardous waste rule for permitted facilities (40 CFR 264.175), and generators have no federal container-containment rule. State rules and permits can be stricter.
The wording “secondary containment requirements OSHA” is one of the most-searched phrases in lab chemical safety, and it is misleading: what applies depends on what is stored, how much, where, and whether it is a product or a waste. This guide sorts the federal rules by storage situation, quotes the numeric limits where a rule sets one, works through sizing examples, and lists what to document. The data table below the guide compares every situation side by side.
What Secondary Containment Is
Secondary containment is a barrier, such as a tray, curbed room, sump, spill pallet or diked area, built around a primary chemical or waste container so that a leak or rupture is captured before it reaches a floor drain, groundwater or an occupied space. The container itself is the primary containment; the tray, curb or dike is the backup.
A working containment system does three things: it holds a defined minimum volume, it is made of a material that will not react with or be dissolved by the liquid it holds, and it has no uncontrolled drain path (no open valve or crack that sends contained liquid to a floor drain or outdoors).
Which Rule Applies: Who Sets What
Four different sources get blended together under the label “OSHA secondary containment”:
- OSHA (29 CFR 1910.106): worker-safety rules for flammable liquids, with containment limited to tank dikes or drainage, outdoor container storage and inside storage rooms.
- EPA RCRA (40 CFR parts 262 and 264): hazardous waste. A containment-system rule exists for permitted storage facilities; generator accumulation rules do not contain one for containers.
- EPA SPCC (40 CFR part 112): oil storage above a capacity threshold.
- Fire code and state or local rules: adopted by the authority having jurisdiction and often more detailed or stricter than the federal text.
Each has its own trigger and capacity formula, so identify the source before you size anything.
Where OSHA Itself Sets a Containment Requirement
Diked areas for aboveground flammable liquid tanks
Under 29 CFR 1910.106(b)(2)(vii)(c), the capacity of a dike around aboveground flammable liquid tanks must be not less than the greatest amount of liquid that can be released from the largest tank in the diked area, with the volume of the other tanks below the height of the dike deducted. The walls must be liquidtight and able to withstand a full hydrostatic head, they may average no more than 6 ft above interior grade, and loose combustible material and drums may not be kept in the diked area. As an alternative to a dike, the drainage provision in 1910.106(b)(2)(vii)(b) requires an impounding basin that is not smaller than the largest tank it serves. Both apply to tank installations, which are rare inside a research building but relevant for institutions with a solvent or fuel tank farm.
Outdoor storage of flammable liquid containers
For containers stored outdoors, 1910.106(d)(6)(iii) requires the area to be graded to divert spills away from buildings or other exposures, or to be surrounded by a curb at least 6 inches high, and to provide drainage of ground or rain water. This is a diversion and drainage requirement, not a percentage-of-volume formula.
Inside storage rooms
For an inside storage room, 1910.106(d)(4)(i) requires that openings to other rooms have noncombustible liquid-tight raised sills or ramps at least 4 inches high, or that the floor be at least 4 inches below the surrounding floor. An open-grated trench draining to a safe location is the other permitted arrangement, and the room must be liquid-tight where the walls meet the floor. A locally adopted fire code may add construction detail, so confirm with the authority having jurisdiction for a specific building.
Flammable liquid storage cabinets
1910.106(d)(3) limits a cabinet to 60 gallons of Category 1, 2 or 3 flammable liquids, or 120 gallons of Category 4. In a metal cabinet the door sill must be raised at least 2 inches above the cabinet bottom. The paragraph contains no sump or spill-containment requirement, so a cabinet is a fire-protection device, not secondary containment. See flammable liquid storage cabinet requirements for the rest of the cabinet rules.
Indoor bench storage and the Laboratory Standard
For bottles on a bench, under a hood or in a general chemical cabinet, 1910.106 sets no containment volume. The Laboratory Standard (29 CFR 1910.1450) requires a Chemical Hygiene Plan that includes standard operating procedures (e)(3)(i), criteria for the use of control measures such as engineering controls, personal protective equipment and hygiene practices (e)(3)(ii), and measures to ensure fume hoods function properly (e)(3)(iii). The standard does not name secondary containment, but the control-measure criteria are where an institution records its tray or bin policy. The wider storage logic is covered in chemical storage compatibility and segregation rules.
The EPA Hazardous Waste Rules (RCRA)
Permitted storage facilities: 40 CFR 264.175
40 CFR 264.170 makes the container-storage rules apply to owners and operators of permitted hazardous waste facilities that store waste in containers. For containers holding free liquids, 264.175(b) requires a containment system with five features:
- A base free of cracks or gaps and sufficiently impervious to contain leaks, spills and accumulated precipitation until collected waste is detected and removed.
- A base sloped or otherwise designed to drain and remove liquids, unless the containers are elevated or otherwise protected from contact with accumulated liquid.
- Capacity of at least 10% of the volume of the containers or the volume of the largest container, whichever is greater. Containers that do not hold free liquids are not counted in this calculation.
- Run-on prevented, unless the system has enough excess capacity to contain it.
- Spilled or leaked waste and accumulated precipitation removed from the sump or collection area as promptly as necessary to prevent overflow.
Areas that hold only waste without free liquids are exempt from (b) if they are sloped or designed to drain, or the containers are elevated. Certain listed wastes (F020 to F023, F026 and F027) still need the full containment system. The section number 265.175, for interim-status facilities, is currently reserved and contains no text.
Generators: satellite and central accumulation areas
Laboratories are usually generators, not permitted facilities, and the generator accumulation rules have no federal secondary-containment requirement for containers:
- Satellite accumulation area (40 CFR 262.15(a)): up to 55 gallons of non-acute hazardous waste, or 1 quart of liquid (1 kg of solid) acute hazardous waste. The container must be in good condition, closed at all times except when waste is added, removed, consolidated or vented, and labelled “Hazardous Waste” with an indication of the hazards. Excess must move within three consecutive calendar days. See satellite accumulation areas.
- Small quantity generator central accumulation area (262.16(b)(2)): container condition and closure rules and at least weekly inspection of the central accumulation area.
- Large quantity generator (262.17(a)(1)): container condition and closure rules and weekly inspection for leaking and deteriorating containers.
Many institutional waste programs and state regulations nonetheless require a tray or bin under waste containers, and use the 264.175(b)(3) capacity formula as their benchmark. That is institutional or state policy, not a federal generator rule. Check the state hazardous waste agency’s rules and any permit before treating a tray as optional.
SPCC: Oil Storage (40 CFR Part 112)
The Spill Prevention, Control, and Countermeasure rule exempts a facility whose aggregate aboveground oil storage capacity is 1,320 US gallons or less (112.1(d)(2)(ii)), and in that count only containers with a capacity of 55 gallons or greater are counted. A completely buried capacity threshold of 42,000 gallons also applies (112.1(d)(2)(i)). Small bottles and drums under 55 gallons therefore do not count toward the aboveground threshold.
For a facility that is covered, 112.8(c)(2) requires bulk storage containers to have secondary containment sized for the entire capacity of the largest single container plus sufficient freeboard for precipitation. For mobile or portable containers, 112.8(c)(11) requires containment sufficient to hold the capacity of the largest single compartment or container; mobile refuelers and non-transportation-related tank trucks are exempt from that paragraph. Paragraph 112.8(c)(6) requires integrity testing of containers on a regular schedule.
Worked Sizing Examples
These use the 264.175(b)(3) formula (greater of 10% of container volume or the largest container) as a benchmark for a shared containment area holding liquids. Compute both numbers and take the larger.
| Containers holding free liquid | Total volume | 10% of total | Largest container | Minimum capacity |
|---|---|---|---|---|
| Four 55-gallon drums | 220 gal | 22 gal | 55 gal | 55 gal (largest container governs) |
| Twenty 4 L bottles | 80 L | 8 L | 4 L | 8 L (10% of total governs) |
| One 200 L drum and ten 20 L carboys | 400 L | 40 L | 200 L | 200 L (largest container governs) |
Two points follow from the arithmetic. With a few large containers the largest one almost always governs, and with many small containers the 10% figure can. Containers that hold no free liquid are excluded from the total, so a solids-only container does not raise the requirement. Note also that the formula contains no “110%” figure; if a policy states 110% of the largest container, that is the institution’s or state’s own choice, and it must be followed where it applies.
The SPCC rule is different: it requires the entire capacity of the largest single container, and the 55-gallon counting rule decides whether the facility is covered at all.
Construction and Material Requirements
Whatever rule sets the size, the system has to work physically:
- Chemical compatibility: the tray, sump or liner must not react with, dissolve in or be permeated by the contents. Polyethylene suits many acids and bases but not many organic solvents; check compatibility the way you would for gloves (see chemical-resistant glove selection).
- No uncontrolled discharge path: a drain valve on a sump should default closed and require a deliberate action to open.
- Structural integrity: no cracks, corrosion or gaps at seams, and a sound, impervious base as 264.175(b)(1) describes. Corrosives accelerate degradation; see corrosive chemicals in the lab.
- Precipitation and run-on for outdoor areas: a cover, or drainage and reserve capacity, as 1910.106(d)(6)(iii) and 264.175(b)(4) and (5) describe.
- Segregation: do not put incompatible chemicals in a shared tray. For large quantity generators, 262.17(a)(1) addresses separation of incompatible waste.
Inspection and Documentation Checklist
- Identify, per storage location, whether the contents are product or waste, flammable liquid or oil, and which rule above applies.
- Record the capacity calculation (total volume, largest container, result) next to the location, as in the worked examples.
- Write the tray or bin policy into the Chemical Hygiene Plan control-measure criteria under 1910.1450(e)(3)(ii).
- Inspect hazardous waste central accumulation areas at least weekly for leaking or deteriorating containers (262.16(b)(2), 262.17(a)(1)).
- Keep a defined interval for non-waste chemical storage trays; no federal interval applies, so set one by policy.
- Where SPCC applies, document integrity testing on the schedule required by 112.8(c)(6).
Common Compliance Mistakes
- Citing “the OSHA 110% rule.” There is no such OSHA rule. The 10%-or-largest-container formula is in EPA’s 40 CFR 264.175(b)(3) and applies to permitted facilities; the 110% wording is not in the rule text.
- Saying RCRA requires secondary containment in every central accumulation area. Federal generator rules (262.15, 262.16, 262.17) do not state one for containers; state rules and permits can.
- Treating a storage cabinet as containment. 1910.106(d)(3) sets fire-resistance and capacity limits and a 2 inch door sill, not a sump.
- Leaving a sump drain valve open. It routes contained liquid to a floor drain and defeats the system.
- Counting small containers toward SPCC. Only containers of 55 gallons or more count toward the 1,320 gallon threshold; the aggregate-volume point does matter for the 10% waste formula, which uses total container volume.
- Treating a spill kit as containment. A chemical spill kit is a response tool used after a release; containment is a passive, always-in-place control.
Frequently Asked Questions
Does OSHA require secondary containment for chemicals?
Not as a general rule. OSHA’s containment provisions are in 29 CFR 1910.106: dikes or drainage for aboveground flammable liquid tanks, grading or a 6 inch curb for outdoor container storage, and liquid-tight sills or ramps at least 4 inches high for inside storage rooms. Indoor bench and cabinet storage has no OSHA containment volume.
What is the 110% secondary containment rule?
It is a common shorthand. The federal text it is usually traced to is 40 CFR 264.175(b)(3): at least 10% of the volume of the containers or the volume of the largest container, whichever is greater, for permitted hazardous waste storage. A 110% figure comes from an institutional or state policy, not that rule.
Does EPA require secondary containment for hazardous waste containers?
For permitted storage facilities, yes (264.175). For generators, the accumulation rules in 262.15, 262.16 and 262.17 do not require it for containers, although states and permits can.
Do satellite accumulation areas need secondary containment?
Federal 262.15(a) does not state one. It requires a container in good condition, closed except when adding, removing, consolidating or venting waste, and labelled. Many institutions and states require a tray anyway.
Does a flammable storage cabinet count as secondary containment?
No. 1910.106(d)(3) limits cabinet capacity (60 gallons Category 1 to 3, 120 gallons Category 4) and requires a door sill at least 2 inches above the cabinet bottom, but sets no sump or spill-containment requirement. A tray inside provides the liquid containment.
How big must a spill pallet or tray be for drums?
Where the 264.175 formula is used as the benchmark, the greater of 10% of total container volume or the largest container: for four 55-gallon drums, 55 gallons. Where SPCC applies, the entire capacity of the largest container plus precipitation freeboard.
How high must a curb be for outdoor flammable liquid storage?
At least 6 inches under 1910.106(d)(6)(iii), unless the area is graded to divert spills away from buildings or exposures. Drainage of ground or rain water must also be provided.
At what size does SPCC apply?
The exemption is for aggregate aboveground oil capacity of 1,320 US gallons or less, counting only containers of 55 gallons or more (112.1(d)(2)(ii)).
How often must hazardous waste storage areas be inspected?
Central accumulation areas must be inspected at least weekly (262.16(b)(2) for small quantity generators; 262.17(a)(1) for large quantity generators, looking for leaking and deteriorating containers). The satellite accumulation text in 262.15(a) has no weekly inspection requirement.
Sources
- OSHA, 29 CFR 1910.106 Flammable liquids: https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.106
- OSHA, 29 CFR 1910.1450 Occupational exposure to hazardous chemicals in laboratories: https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.1450
- eCFR, 40 CFR 264.170 and 264.175 (container storage and containment): https://www.ecfr.gov/current/title-40/section-264.175
- eCFR, 40 CFR 265.175: https://www.ecfr.gov/current/title-40/section-265.175
- eCFR, 40 CFR 262.15 Satellite accumulation area: https://www.ecfr.gov/current/title-40/section-262.15
- eCFR, 40 CFR 262.16 Small quantity generators: https://www.ecfr.gov/current/title-40/section-262.16
- eCFR, 40 CFR 262.17 Large quantity generators: https://www.ecfr.gov/current/title-40/section-262.17
- eCFR, 40 CFR part 112 (SPCC), sections 112.1 and 112.8: https://www.ecfr.gov/current/title-40/part-112
Related Reading
- Chemical Storage Compatibility: Segregation Rules for Acids, Bases, Oxidizers, and Flammables
- Flammable Liquid Storage Cabinet Requirements: OSHA and NFPA Rules Explained
- Satellite Accumulation Areas: Rules for Chemical Waste at the Point of Generation
- Chemical Waste Disposal Procedures for a Closing Laboratory
- Chemical Spill Kits: What to Stock and How to Respond to a Lab Spill
- Corrosive Chemicals in the Lab: Hazards, Handling, and First Aid
- Secondary Container Labeling: OSHA HazCom Rules for Lab Chemicals
Data: Secondary containment and spill-control requirements by storage situation: OSHA 1910.106, RCRA and SPCC
Compares what US federal regulations require for spill containment across chemical and oil storage situations: whether containment is required, its capacity basis and the key numeric limit. Compiled by CASRAI from the current text of 29 CFR 1910.106 (OSHA) and 40 CFR parts 112, 262 and 264 (EPA) as published in eCFR; state rules and permits can be stricter.
Period covered: 2026. Coverage: United States (federal rules).
| Storage situation | Rule | Containment required by this rule | Capacity or design basis | Key numeric limit | Limit unit |
|---|---|---|---|---|---|
| Aboveground flammable liquid tanks in a diked area | 29 CFR 1910.106(b)(2)(vii)(c) | Yes (dike or drainage) | Dike capacity not less than the greatest amount releasable from the largest tank, other tanks' volume below dike height deducted; walls liquidtight | 6 | ft maximum average dike wall height above interior grade |
| Aboveground flammable liquid tanks served by drainage | 29 CFR 1910.106(b)(2)(vii)(b) | Yes (drainage to impounding basin) | Impounding basin not smaller than the largest tank served | n/a | |
| Outdoor storage of flammable liquid containers | 29 CFR 1910.106(d)(6)(iii) | Yes (grading or curb) | Graded to divert spills away from buildings, or surrounded by a curb; provide drainage of ground or rain water | 6 | in. minimum curb height |
| Inside storage room for flammable liquids | 29 CFR 1910.106(d)(4)(i) | Yes (liquid-tight sill, ramp, recessed floor or grated trench) | Noncombustible liquid-tight raised sills or ramps at openings, or floor below surrounding floor, or open-grated trench draining to a safe location | 4 | in. minimum sill or ramp height (or floor depth below surrounding floor) |
| Flammable liquid storage cabinet | 29 CFR 1910.106(d)(3) | No sump or spill containment stated | Cabinet fire-resistance and capacity limits only; metal cabinet door sill raised above cabinet bottom | 60 | gal maximum Category 1-3 flammable liquid per cabinet (120 gal for Category 4; door sill at least 2 in.) |
| Hazardous waste containers at a permitted storage facility | 40 CFR 264.175(b) | Yes (containment system) | Greater of 10% of container volume or volume of largest container; containers without free liquids excluded from the calculation | 10 | % of total container volume, or largest container if greater |
| Hazardous waste containers at an interim-status facility | 40 CFR 265.175 | None stated: section reserved | No text in current eCFR | n/a | |
| Small quantity generator central accumulation area | 40 CFR 262.16(b)(2) | No secondary containment stated for containers | Container condition, closed containers, incompatible wastes not mixed, weekly inspection | 7 | days maximum interval between inspections (at least weekly) |
| Large quantity generator central accumulation area | 40 CFR 262.17(a)(1) | No general secondary containment stated for containers | Weekly inspection; no general container containment stated in the paragraph | 7 | days maximum interval between inspections (at least weekly) |
| Satellite accumulation area | 40 CFR 262.15(a) | No secondary containment stated | Container in good condition, closed, labelled; excess moved within three consecutive calendar days | 55 | gal maximum non-acute hazardous waste |
| Oil bulk storage containers (SPCC) | 40 CFR 112.8(c)(2); 112.1(d)(2)(ii) | Yes, for facilities above the SPCC threshold | Entire capacity of the largest single container plus sufficient freeboard for precipitation; only containers of 55 gal or more count toward the threshold | 1320 | gal aggregate aboveground capacity threshold |
| Mobile or portable oil containers (SPCC) | 40 CFR 112.8(c)(11) | Yes, for facilities above the SPCC threshold | Sufficient to contain the capacity of the largest single compartment or container; mobile refuelers and non-transportation-related tank trucks exempt | n/a |
Sources
- 29 CFR 1910.106 Flammable liquids (OSHA) (accessed 2026-11-22)
- 40 CFR 264.175 Containment (eCFR) (accessed 2026-11-22)
- 40 CFR 265.175 (eCFR) (accessed 2026-11-22)
- 40 CFR 262.15 Satellite accumulation area (eCFR) (accessed 2026-11-22)
- 40 CFR 262.16 Small quantity generators (eCFR) (accessed 2026-11-22)
- 40 CFR 262.17 Large quantity generators (eCFR) (accessed 2026-11-22)
- 40 CFR 112.1 and 112.8 SPCC (eCFR) (accessed 2026-11-22)
Compiled by CASRAI from the sources above. Free to reuse under CC BY 4.0 with attribution.







